BVP:906297
LDC7415-K-V-3W*-AD1,4

From SIEMENS

LDC7415-K-V-3W*-AD1.4 Optional vertical length up to 3.19 m Outgoing feeder 1.4 m
Model
Product designationtrunking unit for LD busbar trunking system
Product type designationLDC7415-K-V-3W*-AD1,4
General technical data
Configuration of the busbarsL1,L2,L3,PEN,L3,L2,L1
Voltage
Insulation voltage
at AC / rated value1 000 V
at DC / rated value1 200 V
Protection class
Protection class IPIP54
Electricity
Number of circuits / in a trunking unit1
Short-time current resistance (Icw) / at 690 V
limited to 0.1 s / rated value130 kA
limited to 1 s / rated value116 kA
Surge current resistance / at 690 V / rated value286 kA
Main circuit
Operating frequency / rated value
minimum16.7 Hz
maximum60 Hz
Operating voltage / at AC
at 50 Hz / rated value / maximum1 000 V
at 60 Hz / rated value / maximum1 000 V
Operating current
for circuit 1 / at AC / at 50 Hz / for horizontal busbar box with flat busbars / rated value / maximum2 600 A
for circuit 1 / at AC / at 50 Hz / for vertical busbar box / rated value3 200 A
for circuit 1 / at AC / at 50 Hz / rated value / maximum3 200 A
for circuit 1 / at AC / at 60 Hz / rated value / maximum3 200 A
Appearance
Colorlight grey
Product details
Product component / Fire shieldingNo
Number
Number of conductors7
Connections
Conductor cross section / of the (PE)N1 022 mm²
Tap-off points
Arrangement of the outgoing pointssingle-sided
Outgoing point distance0 m
Number of outgoing points / maximum1
Mechanical Design
Height180 mm
Width240 mm
Mounting position / of the busbar trunking unithorizontal
Length
of the busbar trunking unit / customized / maximum3.19 m
of the busbar trunking unit / customized / minimum3.01 m
Mounting typeceiling / wall
Material / of the busbarcopper