BVP:201125
LDA1625-KE1

From SIEMENS

LDA1625-KE1 Cable infeed
Model
Product designationfeeder unit for LD busbar trunking system
Protection class
Protection class IPIP54
Main circuit
Operating frequency / rated value
minimum16.7 Hz
maximum60 Hz
Operating voltage / at AC
at 50 Hz / rated value / maximum1 000 V
at 60 Hz / rated value / maximum1 000 V
Operating current
for circuit 1 / at AC / at 50 Hz / for horizontal busbar box with flat busbars / rated value / maximum900 A
for circuit 1 / at AC / at 50 Hz / for vertical busbar box / rated value900 A
for circuit 1 / at AC / at 50 Hz / rated value / maximum700 A
for circuit 1 / at AC / at 60 Hz / for horizontal busbar box with flat busbars / rated value / maximum900 A
for circuit 1 / at AC / at 60 Hz / for vertical busbar box / rated value900 A
for circuit 1 / at AC / at 60 Hz / rated value / maximum700 A
Connections
Connectable conductor cross-section / in the feeder box
maximum300 mm²
Mechanical Design
Height488 mm
Width674 mm
Length0.55 m
Mounting typeceiling / wall
Material / of the busbaraluminium

External links