Product type designation | CP 443-5 Basic |
| SIMATIC NET, CP 443-5 BASIC COMMUNICATIONS PROCESSOR FOR CONNECTING SIMATIC S7-400 TO PROFIBUS, FMS, S5-COMPATIBLE PG/OP AND S7 COMMUNICATION |
Transmission rate |
Transfer rate | |
at the 1st interface / acc. to PROFIBUS | 9.6 kbit/s ... 12 Mbit/s |
Interfaces |
Number of interfaces / acc. to Industrial Ethernet | 0 |
Number of electrical connections | |
at the 1st interface / acc. to PROFIBUS | 1 |
Type of electrical connection | |
at the 1st interface / acc. to PROFIBUS | 9-pin Sub-D socket (RS485) |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage | DC |
Supply voltage / 1 / from backplane bus | 5 V |
Supply voltage | 5 V |
Relative symmetrical tolerance / at DC | |
at 5 V | 5 % |
Power loss [W] | 6.5 W |
Permitted ambient conditions |
Ambient temperature | |
during operation | 0 ... 60 °C |
during storage | -40 ... +70 °C |
during transport | -40 ... +70 °C |
Relative humidity / at 25 °C / without condensation / during operation / maximum | 95 % |
Protection class IP | IP20 |
Design, dimensions and weight |
Module format | Compact module S7-400 single width |
Width | 25 mm |
Height | 290 mm |
Depth | 210 mm |
Net weight | 0.7 kg |
Product properties, functions, components / general |
Number of units | |
per CPU / maximum | 14 |
Note | depending on CPU type |
Performance data / open communication |
Number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum | 32 |
Amount of data | |
as user data per connection / for open communication / by means of SEND/RECEIVE blocks / maximum | 240 byte |
Performance data / FMS functions |
Number of possible connections / for FMS connection / maximum | 48 |
Amount of data / of the variables | |
for READ job / maximum | 237 byte |
for WRITE job / maximum | 233 byte |
Number of variables | |
Configurable from server to FMS partner | 512 |
Loadable from server to FMS partner | 2640 |
Performance data / S7 communication |
Number of possible connections / for S7 communication | |
maximum | 48 |
Performance data / multi-protocol mode |
Number of possible connections / of which 2 reserved for PG/OP communication / with multi-protocol mode / maximum | 59 |
Product functions / management, configuration |
Configuration software | |