| SIMATIC WINAC RTX 2008, SINGLE LICENSE F. 1 INSTALL., R-SW, SW AND DOCU. ON DVD, LICENSE KEY ON USB STICK, CLASS A, 3 LANGUAGES (D,E,F), EXECUTABLE UNDER WIN XP SP2 AND ARDENCE RTX, REFERENCE-HW: SIMATIC PC |
| General information |
| Product type designation | SIMATIC WinAC RTX 2008 |
| Firmware version | V4.4 |
| Engineering with |
| Programming package | STEP 7 V5.4 SP4 or higher + HW update / iMap V3.0 SP1 |
| Memory |
| Work memory |
| integrated | PC RAM can be used (non-paged memory) |
| Load memory |
| integrated RAM, max. | PC RAM can be used (non-paged memory) |
| CPU processing times |
| for bit operations, typ. | 0.004 µs; Typical |
| for fixed point arithmetic, typ. | 0.003 µs; Typical |
| for floating point arithmetic, typ. | 0.004 µs; Typical |
| Reference platform | Pentium 4, 2.4 GHz |
| CPU-blocks |
| DB |
| Number, max. | Limited only by available PC work memory |
| Size, max. | 64 kbyte |
| FB |
| Number, max. | Limited only by available PC work memory |
| Size, max. | 64 kbyte |
| FC |
| Number, max. | Limited only by available PC work memory |
| Size, max. | 64 kbyte |
| OB |
| Number, max. | Limited only by available PC work memory |
| Size, max. | 64 kbyte |
| Number of free cycle OBs | 1; OB 1 |
| Number of time alarm OBs | 1; OB 10 |
| Number of delay alarm OBs | 1; OB 20 |
| Number of cyclic interrupt OBs | 9; OB 30-38 |
| Number of process alarm OBs | 1; OB 40 |
| Number of ODK OBs | 3; OB 52-54 |
| Number of DPV1 alarm OBs | 3; OB 55-57 |
| Number of isochronous mode OBs | 2; OB 61-62 |
| Number of startup OBs | 2; OB 100, 102 |
| Number of asynchronous error OBs | 7; OB 80, 82-85, 86, 88 |
| Number of synchronous error OBs | 2; OB 121, 122 |
| Nesting depth |
| per priority class | 24 |
| additional within an error OB | 24 |
| Counters, timers and their retentivity |
| S7 counter |
| Number | 2 048 |
| Retentivity |
| — adjustable | Yes |
| — lower limit | 0 |
| — upper limit | 2 047 |
| — preset | 8 |
| Counting range |
| — adjustable | Yes |
| — lower limit | 0 |
| — upper limit | 999 |
| IEC counter |
| present | Yes |
| Type | SFB |
| S7 times |
| Number | 2 048 |
| Retentivity |
| — adjustable | Yes |
| — lower limit | 0 |
| — upper limit | 2 047 |
| — preset | 0 |
| Time range |
| — lower limit | 10 ms |
| — upper limit | 9 990 s |
| IEC timer |
| present | Yes |
| Type | SFB |
| Data areas and their retentivity |
| Retentivity without UPS and PS Extension Board | 128 KB with SIMATIC Microbox PC 427B and Panel PC 477B; other SIMATIC PCs on request |
| Retentivity with UPS | all data |
| Flag |
| Number, max. | 16 kbyte |
| of which retentive | MB 0 to MB 16383 |
| Retentivity preset | MB 0 to MB 15 |
| Number of clock memories | 8 |
| Address area |
| I/O address area |
| Inputs | 16 kbyte |
| Outputs | 16 kbyte |
| Process image |
| Inputs, adjustable | 8 kbyte |
| Outputs, adjustable | 8 kbyte |
| Inputs, default | 512 byte |
| Outputs, default | 512 byte |
| Subprocess images |
| Number of subprocess images, max. | 15 |
| Digital channels |
| Inputs | 128 000 |
| Outputs | 128 000 |
| Analog channels |
| Inputs | 8 000 |
| Outputs | 8 000 |
| Hardware configuration |
| Number of operable FMs and CPs (recommended) |
| FM | 4; FM distributed: FM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2 |
| CP, PtP | 2; CP 340, CP 341 distributed |
| CP, LAN | Over PC CP |
| Submodules |
| Number of submodules, max | 4 |
| — of which PROFIBUS, max. | 4; CP 5611, CP 5611-A2, integrated PROFIBUS interface of the SIMATIC PC, CP 5613 CP, 5613-A2, CP 5603 |
| — of which Industrial Ethernet, max. | 1; PROFINET: CP 1616, CP 1604, S7-mEC integrated PROFINET interface and SIMATIC PC |
| Time of day |
| Clock |
| Hardware clock (real-time) | Yes |
| retentive and synchronizable | Yes |
| Clock synchronization |
| supported | Yes |
| to PC-CP, slave | Yes |
| on Ethernet via NTP | Yes |
| 1. Interface |
| Interface type | CP 5611, CP 5611-A2, integrated PROFIBUS interface of the SIMATIC PC |
| Physics | RS 485 / PROFIBUS |
| Isolated | Yes |
| Number of simultaneously operable CPs, max. | 1 |
| Protocols |
| MPI | No |
| PROFIBUS DP master | Yes |
| PROFIBUS DP slave | No |
| PROFIBUS DP master |
| Number of connections, max. | 8 |
| Transmission rate, max. | 12 Mbit/s |
| Number of DP slaves, max. | 64 |
| Services |
| — PG/OP communication | Yes |
| — Routing | Yes |
| — Global data communication | No |
| — S7 basic communication | No |
| — S7 communication | Yes |
| — Equidistance | Yes; Only in conjunction with isochronous mode |
| — Isochronous mode | Yes |
| — SYNC/FREEZE | Yes |
| — Activation/deactivation of DP slaves | Yes |
| — Direct data exchange (slave-to-slave communication) | Yes |
| — DPV0 | Yes |
| — DPV1 | Yes |
| Address area |
| — Inputs, max. | 16 kbyte |
| — Outputs, max. | 16 kbyte |
| User data per DP slave |
| — Inputs, max. | 244 byte |
| — Outputs, max. | 244 byte |
| 2. Interface |
| Interface type | CP 5613, CP 5613-A2 |
| Physics | RS 485 / PROFIBUS |
| Isolated | Yes |
| Number of simultaneously operable CPs, max. | 4 |
| Protocols |
| MPI | No |
| PROFIBUS DP master | Yes |
| PROFIBUS DP slave | No |
| PROFIBUS DP master |
| Number of connections, max. | 50 |
| Transmission rate, max. | 12 Mbit/s |
| Number of DP slaves, max. | 125 |
| Services |
| — PG/OP communication | Yes |
| — Routing | Yes |
| — Global data communication | No |
| — S7 basic communication | No |
| — S7 communication | Yes |
| — Equidistance | Yes; Only in conjunction with isochronous mode |
| — Isochronous mode | Yes |
| — SYNC/FREEZE | Yes |
| — Activation/deactivation of DP slaves | Yes |
| — Direct data exchange (slave-to-slave communication) | Yes |
| — DPV0 | Yes |
| — DPV1 | Yes |
| Address area |
| — Inputs, max. | 16 kbyte |
| — Outputs, max. | 16 kbyte |
| User data per DP slave |
| — Inputs, max. | 244 byte |
| — Outputs, max. | 244 byte |
| 3. Interface |
| Interface type | PROFINET |
| Physics | Ethernet |
| Isolated | Yes |
| Number of simultaneously operable CPs, max. | 1; Intel Pro/1000 (Intel 82573L, 82541PI; non-shared IRQ required); integrated IE interface SIMATIC PC 4x7B, 6x7B, 8x7B |
| automatic detection of transmission rate | Yes; 10/100 Mbit/s |
| Protocols |
| PROFINET IO Controller | Yes |
| PROFINET IO Device | No |
| PROFINET CBA | Yes |
| Open IE communication | Yes |
| Web server | No |
| PROFINET IO Controller |
| Transmission rate, max. | 100 Mbit/s |
| Services |
| — PG/OP communication | Yes |
| — S7 routing | Yes |
| — S7 communication | Yes |
| — Open IE communication | Yes |
| — IRT | No |
| — Prioritized startup | Yes |
| — Number of IO devices with prioritized startup, max. | 32 |
| — Number of connectable IO Devices, max. | 128 |
| — Activation/deactivation of IO Devices | Yes |
| — IO Devices changing during operation (partner ports), supported | Yes |
| — Device replacement without swap medium | Yes |
| — Send cycles | 1 - 512 ms |
| — Updating time | 1 to 512 ms (minimum value depends on communication share set for PROFINET I/O, on the number of I/O devices, and on the volume of configured user data) |
| Address area |
| — Inputs, max. | 16 kbyte |
| — Outputs, max. | 16 kbyte |
| — User data per address area, max. | 2 kbyte |
| — User data consistency, max. | 256 byte |
| PROFINET CBA |
| acyclic transmission | Yes |
| cyclic transmission | Yes |
| Open IE communication |
| Number of connections, max. | 32 |
| SIMATIC communication |
| Number of connections, max. | 16 |
| 4. Interface |
| Interface type | PROFINET |
| Physics | Ethernet |
| Isolated | Yes |
| Number of simultaneously operable CPs, max. | 1; CP 1616 (HW release 8 or above), CP 1604 (HW release 7 or higher), integrated PROFINET interface of SIMATIC PC and S7-mEC |
| automatic detection of transmission rate | Yes; 10/100 Mbit/s |
| Protocols |
| PROFINET IO Controller | Yes |
| PROFINET CBA | Yes |
| Open IE communication | Yes |
| Web server | No |
| PROFINET IO Controller |
| Transmission rate, max. | 100 Mbit/s |
| Services |
| — PG/OP communication | Yes |
| — S7 routing | Yes |
| — S7 communication | Yes |
| — Open IE communication | Yes |
| — IRT | Yes |
| — Prioritized startup | Yes |
| — Number of IO devices with prioritized startup, max. | 32 |
| — Number of connectable IO Devices, max. | 256 |
| — Number of IO Devices with IRT and the option "high flexibility" | 64 |
| — of which in line, max. | 32 |
| — Activation/deactivation of IO Devices | Yes |
| — Number of IO Devices that can be simultaneously activated/deactivated, max. | 8 |
| — IO Devices changing during operation (partner ports), supported | Yes |
| — Device replacement without swap medium | Yes |
| — Send cycles | 250 µs, 500 µs, 1 ms |
| — Updating time | 0.25...512 depending on the send cycle |
| Address area |
| — Inputs, max. | 16 kbyte |
| — Outputs, max. | 16 kbyte |
| — User data per address area, max. | 2 kbyte |
| — User data consistency, max. | 256 byte |
| Open IE communication |
| Number of connections, max. | 16 |
| SIMATIC communication |
| Number of connections, max. | 32 |
| Protocols |
| Open IE communication |
| TCP/IP | Yes |
| — Number of connections, max. | Dependent on interface |
| — Data length, max. | 8 192 byte |
| ISO-on-TCP (RFC1006) | No |
| UDP | Yes |
| — Number of connections, max. | Dependent on interface |
| — Data length, max. | 1 472 byte |
| Web server |
| supported | No |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) | Yes; only PROFIBUS |
| Equidistance | Yes |
| Number of DP masters with isochronous mode | 2 |
| User data per isochronous slave, max. | 128 byte |
| shortest clock pulse | 2.2 ms; 2.2 ms without partial process image; 2.2 ms with partial process image |
| Communication functions |
| PG/OP communication | Yes |
| Global data communication |
| supported | No |
| S7 basic communication |
| supported | No |
| S7 communication |
| supported | Yes |
| as server | Yes |
| as client | Yes |
| PROFINET CBA (at set setpoint communication load) |
| Setpoint for the CPU communication load | 20 % |
| Number of remote interconnection partners | 64 |
| Number of functions, master/slave | 30 |
| Total of all master/slave connections | 1 000 |
| Data length of all incoming connections master/slave, max. | 6 800 byte |
| Data length of all outgoing connections master/slave, max. | 6 800 byte |
| Number of device-internal and PROFIBUS interconnections | 500 |
| Data length of device-internal und PROFIBUS interconnections, max. | 4 000 byte |
| Data length per connection, max. | 1 400 byte |
| Remote interconnections with acyclic transmission |
| — Sampling frequency: Sampling time, min. | 500 ms |
| — Number of incoming interconnections | 100 |
| — Number of outgoing interconnections | 100 |
| — Data length of all incoming interconnections, max. | 2 000 byte |
| — Data length of all outgoing interconnections, max. | 2 000 byte |
| — Data length per connection, max. | 1 400 byte |
| Remote interconnections with cyclic transmission |
| — Transmission frequency: Transmission interval, min. | 10 ms |
| — Number of incoming interconnections | 200 |
| — Number of outgoing interconnections | 200 |
| — Data length of all incoming interconnections, max. | 4 800 byte |
| — Data length of all outgoing interconnections, max. | 4 800 byte |
| — Data length per connection, max. | 250 byte |
| HMI variables via PROFINET (acyclic) |
| — Number of stations that can log on for HMI variables (PN OPC/iMap) | 3 |
| — HMI variable updating | 500 ms |
| — Number of HMI variables | 200 |
| — Data length of all HMI variables, max. | 2 000 byte |
| PROFIBUS proxy functionality |
| — supported | Yes |
| — Number of linked PROFIBUS devices | 16 |
| — Data length per connection, max. | 240 byte; Slave-dependent |
| Number of connections |
| overall | 64 |
| usable for PG communication | |
| — reserved for PG communication | 1 |
| usable for OP communication | |
| — reserved for OP communication | 1 |
| S7 message functions |
| Number of login stations for message functions, max. | 62 |
| SCAN procedure | No |
| Process diagnostic messages | Yes; ALARM_S, ALARM_SQ |
| simultaneously active Alarm-S blocks, max. | 20; of a total of 20 for all SFCs |
| Alarm 8-blocks | Yes |
| Number of instances for alarm 8 and S7 communication blocks, max. | 600 |
| Process control messages | No |
| Test commissioning functions |
| Status block | Yes |
| Single step | Yes |
| Status/control |
| Status/control variable | Yes |
| Forcing |
| Forcing | No |
| Diagnostic buffer |
| present | Yes |
| Number of entries, max. | |
| — preset | 120 |
| Hardware requirement |
| Hardware required | PC with color monitor, keyboard, mouse or pointing device for Windows |
| Processor |
| Processor | Intel Celeron M, 900 MHz or compatible |
| — Multi-processor system | Yes; Dual Pentium, CoreDuo, Core2Duo or compatible |
| — Hyper-threading | Yes |
| Memory |
| Main memory, min. | 1 Gbyte |
| Required memory on hard disk | 100 Mbyte |
| Operating systems |
| pre-installed operating system |
| Windows NT 4.0 | No |
| Windows 2000 | No |
| Windows Vista | No |
| Windows XP | Yes; Professional, SP2; SP3 WinAC RTX 2008 SP1 or higher |
| Windows XP Embedded | Yes; With the delivery image of the SIMATIC PC |
| — supported HAL types under Windows XP | PC with single core processor without Hyper-Threading: ACPI-PC, ACPI uniprocessor PC; PC with multicore processors or Hyper-Threading: ACPI multiprocessor PC, MPS multiprocessor PC |
| Configuration |
| Configuration software |
| STEP 7 | Yes; V5.4, SP4 or higher, Engineering Tools (optional) |
| Programming |
| Nesting levels | 8 |
| Programming language |
| — LAD | Yes |
| — FBD | Yes |
| — STL | Yes |
| — SCL | Yes |
| — CFC | Yes |
| — GRAPH | Yes |
| — HiGraph® | Yes |
| Software libraries |
| — Easy Motion Control | Yes |
| — Software redundancy | Yes; As of V1.2, only operation of WinAC RTX with WinAC RTX |
| Number of simultaneously active SFCs |
| — DPSYC_FR | 20; of a total of 20 for all SFCs |
| — D_ACT_DP | 20; of a total of 20 for all SFCs |
| — RD_REC | 20; of a total of 20 for all SFCs |
| — WR_REC | 20; of a total of 20 for all SFCs |
| — WR_PARM | 20; of a total of 20 for all SFCs |
| — PARM_MOD | 20; of a total of 20 for all SFCs |
| — WR_DPARM | 20; of a total of 20 for all SFCs |
| — DPNRM_DG | 20; of a total of 20 for all SFCs |
| — RDSYSST | 20; of a total of 20 for all SFCs |
| Number of simultaneously active SFBs |
| — RDREC | 20; of a total of 20 for all SFBs |
| — WRREC | 20; of a total of 20 for all SFBs |
| Know-how protection |
| User program protection/password protection | Yes |
| Open Development interfaces |
| CCX (Custom Code Extension) | Yes; WinAC ODK V4.1 or higher |
| CMI (Controller Management Interface) | Yes; WinAC ODK V4.1 or higher |
| SMX (Shared Memory Extension) | Yes; WinAC ODK V4.1 or higher |
| — Inputs | 4 kbyte |
| — Outputs | 4 kbyte |
| Weights |
| Weight, approx. | 100 g; With packaging |
| last modified: | 03/12/2019 |