6ES7671-0RC06-0YA0
SIMATIC WINAC RTX 2008

From SIEMENS

SIMATIC WINAC RTX 2008, SINGLE LICENSE F. 1 INSTALL., R-SW, SW AND DOCU. ON DVD, LICENSE KEY ON USB STICK, CLASS A, 3 LANGUAGES (D,E,F), EXECUTABLE UNDER WIN XP SP2 AND ARDENCE RTX, REFERENCE-HW: SIMATIC PC
General information
Product type designationSIMATIC WinAC RTX 2008
Firmware versionV4.4
Engineering with
Programming packageSTEP 7 V5.4 SP4 or higher + HW update / iMap V3.0 SP1
Memory
Work memory
integratedPC RAM can be used (non-paged memory)
Load memory
integrated RAM, max.PC RAM can be used (non-paged memory)
CPU processing times
for bit operations, typ.0.004 µs; Typical
for fixed point arithmetic, typ.0.003 µs; Typical
for floating point arithmetic, typ.0.004 µs; Typical
Reference platformPentium 4, 2.4 GHz
CPU-blocks
DB
Number, max.Limited only by available PC work memory
Size, max.64 kbyte
FB
Number, max.Limited only by available PC work memory
Size, max.64 kbyte
FC
Number, max.Limited only by available PC work memory
Size, max.64 kbyte
OB
Number, max.Limited only by available PC work memory
Size, max.64 kbyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of delay alarm OBs1; OB 20
Number of cyclic interrupt OBs9; OB 30-38
Number of process alarm OBs1; OB 40
Number of ODK OBs3; OB 52-54
Number of DPV1 alarm OBs3; OB 55-57
Number of isochronous mode OBs2; OB 61-62
Number of startup OBs2; OB 100, 102
Number of asynchronous error OBs7; OB 80, 82-85, 86, 88
Number of synchronous error OBs2; OB 121, 122
Nesting depth
per priority class24
additional within an error OB24
Counters, timers and their retentivity
S7 counter
Number2 048
Retentivity
— adjustableYes
— lower limit0
— upper limit2 047
— preset8
Counting range
— adjustableYes
— lower limit0
— upper limit999
IEC counter
presentYes
TypeSFB
S7 times
Number2 048
Retentivity
— adjustableYes
— lower limit0
— upper limit2 047
— preset0
Time range
— lower limit10 ms
— upper limit9 990 s
IEC timer
presentYes
TypeSFB
Data areas and their retentivity
Retentivity without UPS and PS Extension Board128 KB with SIMATIC Microbox PC 427B and Panel PC 477B; other SIMATIC PCs on request
Retentivity with UPSall data
Flag
Number, max.16 kbyte
of which retentiveMB 0 to MB 16383
Retentivity presetMB 0 to MB 15
Number of clock memories8
Address area
I/O address area
Inputs16 kbyte
Outputs16 kbyte
Process image
Inputs, adjustable8 kbyte
Outputs, adjustable8 kbyte
Inputs, default512 byte
Outputs, default512 byte
Subprocess images
Number of subprocess images, max.15
Digital channels
Inputs128 000
Outputs128 000
Analog channels
Inputs8 000
Outputs8 000
Hardware configuration
Number of operable FMs and CPs (recommended)
FM4; FM distributed: FM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2
CP, PtP2; CP 340, CP 341 distributed
CP, LANOver PC CP
Submodules
Number of submodules, max4
— of which PROFIBUS, max.4; CP 5611, CP 5611-A2, integrated PROFIBUS interface of the SIMATIC PC, CP 5613 CP, 5613-A2, CP 5603
— of which Industrial Ethernet, max.1; PROFINET: CP 1616, CP 1604, S7-mEC integrated PROFINET interface and SIMATIC PC
Time of day
Clock
Hardware clock (real-time)Yes
retentive and synchronizableYes
Clock synchronization
supportedYes
to PC-CP, slaveYes
on Ethernet via NTPYes
1. Interface
Interface typeCP 5611, CP 5611-A2, integrated PROFIBUS interface of the SIMATIC PC
PhysicsRS 485 / PROFIBUS
IsolatedYes
Number of simultaneously operable CPs, max.1
Protocols
MPINo
PROFIBUS DP masterYes
PROFIBUS DP slaveNo
PROFIBUS DP master
Number of connections, max.8
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.64
Services
— PG/OP communicationYes
— RoutingYes
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationYes
— EquidistanceYes; Only in conjunction with isochronous mode
— Isochronous modeYes
— SYNC/FREEZEYes
— Activation/deactivation of DP slavesYes
— Direct data exchange (slave-to-slave communication)Yes
— DPV0Yes
— DPV1Yes
Address area
— Inputs, max.16 kbyte
— Outputs, max.16 kbyte
User data per DP slave
— Inputs, max.244 byte
— Outputs, max.244 byte
2. Interface
Interface typeCP 5613, CP 5613-A2
PhysicsRS 485 / PROFIBUS
IsolatedYes
Number of simultaneously operable CPs, max.4
Protocols
MPINo
PROFIBUS DP masterYes
PROFIBUS DP slaveNo
PROFIBUS DP master
Number of connections, max.50
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.125
Services
— PG/OP communicationYes
— RoutingYes
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationYes
— EquidistanceYes; Only in conjunction with isochronous mode
— Isochronous modeYes
— SYNC/FREEZEYes
— Activation/deactivation of DP slavesYes
— Direct data exchange (slave-to-slave communication)Yes
— DPV0Yes
— DPV1Yes
Address area
— Inputs, max.16 kbyte
— Outputs, max.16 kbyte
User data per DP slave
— Inputs, max.244 byte
— Outputs, max.244 byte
3. Interface
Interface typePROFINET
PhysicsEthernet
IsolatedYes
Number of simultaneously operable CPs, max.1; Intel Pro/1000 (Intel 82573L, 82541PI; non-shared IRQ required); integrated IE interface SIMATIC PC 4x7B, 6x7B, 8x7B
automatic detection of transmission rateYes; 10/100 Mbit/s
Protocols
PROFINET IO ControllerYes
PROFINET IO DeviceNo
PROFINET CBAYes
Open IE communicationYes
Web serverNo
PROFINET IO Controller
Transmission rate, max.100 Mbit/s
Services
— PG/OP communicationYes
— S7 routingYes
— S7 communicationYes
— Open IE communicationYes
— IRTNo
— Prioritized startupYes
— Number of IO devices with prioritized startup, max.32
— Number of connectable IO Devices, max.128
— Activation/deactivation of IO DevicesYes
— IO Devices changing during operation (partner ports), supportedYes
— Device replacement without swap mediumYes
— Send cycles1 - 512 ms
— Updating time1 to 512 ms (minimum value depends on communication share set for PROFINET I/O, on the number of I/O devices, and on the volume of configured user data)
Address area
— Inputs, max.16 kbyte
— Outputs, max.16 kbyte
— User data per address area, max.2 kbyte
— User data consistency, max.256 byte
PROFINET CBA
acyclic transmissionYes
cyclic transmissionYes
Open IE communication
Number of connections, max.32
SIMATIC communication
Number of connections, max.16
4. Interface
Interface typePROFINET
PhysicsEthernet
IsolatedYes
Number of simultaneously operable CPs, max.1; CP 1616 (HW release 8 or above), CP 1604 (HW release 7 or higher), integrated PROFINET interface of SIMATIC PC and S7-mEC
automatic detection of transmission rateYes; 10/100 Mbit/s
Protocols
PROFINET IO ControllerYes
PROFINET CBAYes
Open IE communicationYes
Web serverNo
PROFINET IO Controller
Transmission rate, max.100 Mbit/s
Services
— PG/OP communicationYes
— S7 routingYes
— S7 communicationYes
— Open IE communicationYes
— IRTYes
— Prioritized startupYes
— Number of IO devices with prioritized startup, max.32
— Number of connectable IO Devices, max.256
— Number of IO Devices with IRT and the option "high flexibility"64
— of which in line, max.32
— Activation/deactivation of IO DevicesYes
— Number of IO Devices that can be simultaneously activated/deactivated, max.8
— IO Devices changing during operation (partner ports), supportedYes
— Device replacement without swap mediumYes
— Send cycles250 µs, 500 µs, 1 ms
— Updating time0.25...512 depending on the send cycle
Address area
— Inputs, max.16 kbyte
— Outputs, max.16 kbyte
— User data per address area, max.2 kbyte
— User data consistency, max.256 byte
Open IE communication
Number of connections, max.16
SIMATIC communication
Number of connections, max.32
Protocols
Open IE communication
TCP/IPYes
— Number of connections, max.Dependent on interface
— Data length, max.8 192 byte
ISO-on-TCP (RFC1006)No
UDPYes
— Number of connections, max.Dependent on interface
— Data length, max.1 472 byte
Web server
supportedNo
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes; only PROFIBUS
EquidistanceYes
Number of DP masters with isochronous mode2
User data per isochronous slave, max.128 byte
shortest clock pulse2.2 ms; 2.2 ms without partial process image; 2.2 ms with partial process image
Communication functions
PG/OP communicationYes
Global data communication
supportedNo
S7 basic communication
supportedNo
S7 communication
supportedYes
as serverYes
as clientYes
PROFINET CBA (at set setpoint communication load)
Setpoint for the CPU communication load20 %
Number of remote interconnection partners64
Number of functions, master/slave30
Total of all master/slave connections1 000
Data length of all incoming connections master/slave, max.6 800 byte
Data length of all outgoing connections master/slave, max.6 800 byte
Number of device-internal and PROFIBUS interconnections500
Data length of device-internal und PROFIBUS interconnections, max.4 000 byte
Data length per connection, max.1 400 byte
Remote interconnections with acyclic transmission
— Sampling frequency: Sampling time, min.500 ms
— Number of incoming interconnections100
— Number of outgoing interconnections100
— Data length of all incoming interconnections, max.2 000 byte
— Data length of all outgoing interconnections, max.2 000 byte
— Data length per connection, max.1 400 byte
Remote interconnections with cyclic transmission
— Transmission frequency: Transmission interval, min.10 ms
— Number of incoming interconnections200
— Number of outgoing interconnections200
— Data length of all incoming interconnections, max.4 800 byte
— Data length of all outgoing interconnections, max.4 800 byte
— Data length per connection, max.250 byte
HMI variables via PROFINET (acyclic)
— Number of stations that can log on for HMI variables (PN OPC/iMap)3
— HMI variable updating500 ms
— Number of HMI variables200
— Data length of all HMI variables, max.2 000 byte
PROFIBUS proxy functionality
— supportedYes
— Number of linked PROFIBUS devices16
— Data length per connection, max.240 byte; Slave-dependent
Number of connections
overall64
usable for PG communication
— reserved for PG communication1
usable for OP communication
— reserved for OP communication1
S7 message functions
Number of login stations for message functions, max.62
SCAN procedureNo
Process diagnostic messagesYes; ALARM_S, ALARM_SQ
simultaneously active Alarm-S blocks, max.20; of a total of 20 for all SFCs
Alarm 8-blocksYes
Number of instances for alarm 8 and S7 communication blocks, max.600
Process control messagesNo
Test commissioning functions
Status blockYes
Single stepYes
Status/control
Status/control variableYes
Forcing
ForcingNo
Diagnostic buffer
presentYes
Number of entries, max.
— preset120
Hardware requirement
Hardware requiredPC with color monitor, keyboard, mouse or pointing device for Windows
Processor
ProcessorIntel Celeron M, 900 MHz or compatible
— Multi-processor systemYes; Dual Pentium, CoreDuo, Core2Duo or compatible
— Hyper-threadingYes
Memory
Main memory, min.1 Gbyte
Required memory on hard disk100 Mbyte
Operating systems
pre-installed operating system
Windows NT 4.0No
Windows 2000No
Windows VistaNo
Windows XPYes; Professional, SP2; SP3 WinAC RTX 2008 SP1 or higher
Windows XP EmbeddedYes; With the delivery image of the SIMATIC PC
— supported HAL types under Windows XPPC with single core processor without Hyper-Threading: ACPI-PC, ACPI uniprocessor PC; PC with multicore processors or Hyper-Threading: ACPI multiprocessor PC, MPS multiprocessor PC
Configuration
Configuration software
STEP 7Yes; V5.4, SP4 or higher, Engineering Tools (optional)
Programming
Nesting levels8
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— CFCYes
— GRAPHYes
— HiGraph®Yes
Software libraries
— Easy Motion ControlYes
— Software redundancyYes; As of V1.2, only operation of WinAC RTX with WinAC RTX
Number of simultaneously active SFCs
— DPSYC_FR20; of a total of 20 for all SFCs
— D_ACT_DP20; of a total of 20 for all SFCs
— RD_REC20; of a total of 20 for all SFCs
— WR_REC20; of a total of 20 for all SFCs
— WR_PARM20; of a total of 20 for all SFCs
— PARM_MOD20; of a total of 20 for all SFCs
— WR_DPARM20; of a total of 20 for all SFCs
— DPNRM_DG20; of a total of 20 for all SFCs
— RDSYSST20; of a total of 20 for all SFCs
Number of simultaneously active SFBs
— RDREC20; of a total of 20 for all SFBs
— WRREC20; of a total of 20 for all SFBs
Know-how protection
User program protection/password protectionYes
Open Development interfaces
CCX (Custom Code Extension)Yes; WinAC ODK V4.1 or higher
CMI (Controller Management Interface)Yes; WinAC ODK V4.1 or higher
SMX (Shared Memory Extension)Yes; WinAC ODK V4.1 or higher
— Inputs4 kbyte
— Outputs4 kbyte
Weights
Weight, approx.100 g; With packaging
last modified:03/12/2019