6ES7655-5DX60-1BB0
ACTIVE FIELD DISTRIBUTOR AFDISD

From SIEMENS

Active field distributor AFDiSD FISCO field barrier for PROFIBUS PA for Foundation Fieldbus H1 Extended fieldbus diagnostics for PROFIBUS PA 6 short circuit-proof and intrinsically safe spur lines with bounce protection logic Integrated field bus repeater Automatic bus termination for line and ring topology for extended temperature range Degree of protection IP66 Extended fieldbus diagnostics
General information
Product type designationAFDiSD active field distributor
HW functional status01
Product descriptionActive field distributor with diagnostics
Product function
Repeater functionYes
Supply voltage
Design of the power supplyvia fieldbus
permissible range, lower limit (DC)16 V
permissible range, upper limit (DC)32 V
Reverse polarity protectionYes; only in conjunction with FDC 157
Overvoltage protectionYes; only in conjunction with FDC 157
Input current
Current consumption, max.400 mA; at 20 V input voltage
Current consumption in the case of short-circuit at all spur lines100 mA; at 24 V input voltage
Power loss
Power loss, typ.1.4 W; minimum - typ. specification not possible because load-dependent
Power loss, max.5.9 W
Interfaces
PROFIBUS PA
Transmission rate, max.31.25 kbit/s
Number of connectable PA field devices6
Current output to PA field devices, max.260 mA; max. 180 mA total current of all field devices for operation in the permissible operating voltage range from 16 V to 32 V
permissible current per spur line40 mA; first spur line 60 mA
Protocols
PROFIBUS DPNo
PROFIBUS PAYes
AS-InterfaceNo
FOUNDATION Fieldbus H1Yes
Interrupts/diagnostics/status information
Status indicatorYes
AlarmsNo
Diagnostics functionYes
Diagnostics indication LED
Main line statusYes
Main line failureYes
Spur line status/faultYes
automatic bus terminationYes
Potential separation
between main line and spur linesYes
Isolation
Isolation tested with2 550 V DC
Degree and class of protection
Degree of protection acc. to EN 60529
IP66Yes
Standards, approvals, certificates
Use in hazardous areas
ATEX Zone 1Yes
ATEX Zone 21Yes
ATEX Zone 2Yes
ATEX Zone 22Yes
FM Class I Zone 1No
FM Class I Zone 2, Division 2No
Type of protection acc. to KEMA14 ATEX 0044
Test number KEMA14 ATEX 0044
Ambient conditions
Ambient temperature during operation
min.-40 °C
max.70 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Relative humidity
Operation, max.95 %
Connection method
Main line
Number of main lines2
Design of terminalsScrew terminal block
Type of connection (enclosure cable gland)M20
Type of cableType A
Cable diameter, min.6 mm
Cable diameter, max.13 mm
Conductor cross-section, min.0.2 mm²
Conductor cross-section, max.2.5 mm²
automatic bus terminationYes
permissible main line current1 A
Spur line
Number of spur lines6
Design of terminalsScrew terminal block
Type of connection (enclosure cable gland)M16
Type of cableType A
Cable diameter, min.4 mm
Cable diameter, max.9 mm
Conductor cross-section, min.0.2 mm²
Conductor cross-section, max.2.5 mm²
total current output to field devices, max.260 mA; max. 180 mA total current of all field devices for operation in the permissible operating voltage range from 16 V to 32 V
Number of connectable field devices6
Current limitation per field device, max.40 mA; 60 mA on S1
No-load voltage, max.15.3 V
short-circuit proofYes
Short-circuit current (test current); max.6 mA
intrinsically safe according to FISCO modelYes
Debounce logicYes
Dimensions
Width380 mm
Height85 mm
Depth170 mm
Weights
Weight, approx.4 500 g
last modified:03/25/2019