| *** SPARE PART*** SIMATIC C7-634/P, COMPACT UNIT WITH INTEGRATED COMPONENTS: S7-300 CPU 315, OP17, IM 360 16DI, 16DO, 4AI, 4AO, 4 UI |
Operator control and monitoring |
Password protection | Yes |
Password levels | 9 |
Graphics object |
Character graphics | Yes; As part of the character set |
Process images |
Number of process images | 99 |
Number of variables in message text, max. | 8 |
Entries per process image | 99 |
Operating-/fault messages |
Number of operating messages, max. | 999 |
Scroll operating messages, max. | 256 |
Number of entries in operational log, max. | 256 |
Number of fault message, max. | 999 |
Number of entries in fault message buffer, max. | 256 |
Number of symbol/character sets | 1 |
Recipes |
Number, max. | 99 |
Data records per recipe, max. | 99 |
Entries per data record, max. | 99 |
Recipe data memory, max. | 20 kbyte |
Display |
Design of display | LCD backlit |
dynamic objects | Input, output, input/output fields, date/time fields, symbolic input/output fields |
Line display |
Number of lines | 8; 4x 20 / 8x 40 |
Number of characters per line | 40; 4x 20 / 8x 40 |
Character size | 6 mm; 11/6 mm |
Backlighting |
MTBF backlighting (at 25 °C) | 100 000 h; about 11 years |
Control elements |
Keyboard fonts |
Function keys | |
— Number of function keys | 16 |
— Number of softkeys | 8 |
Supply voltage |
Rated value (DC) | |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 30.2 V |
Load voltage L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current |
Current consumption, typ. | 550 mA |
Current consumption, max. | 1 A |
Power loss |
Power loss, typ. | 12 W |
Memory |
Work memory |
integrated | 48 kbyte; 16 K instructions RAM |
Load memory |
expandable FEPROM | Yes |
expandable FEPROM, max. | 512 kbyte |
integrated RAM, max. | 80 kbyte; for data |
Backup |
with battery | Yes; all data |
without battery | Yes; 4736 Byte: parameterizable for memory bits, times, counters, data |
CPU processing times |
for bit operations, typ. | 0.3 µs |
for bit operations, max. | 0.6 µs |
for word operations, typ. | 1 µs |
for fixed point arithmetic, typ. | 2 µs |
for floating point arithmetic, typ. | 50 µs |
for timer/counter operations, typ. | 12 µs |
CPU-blocks |
DB |
Number, max. | 255; DB 0 reserved |
FB |
Number, max. | 192; see instruction list |
FC |
Number, max. | 192; see instruction list |
OB |
Number, max. | see instruction list |
Number of free cycle OBs | 1; OB 1 |
Number of time alarm OBs | 1; OB 10 |
Number of cyclic interrupt OBs | 1; OB 35 |
Number of process alarm OBs | 1; OB 40 |
Number of startup OBs | 1; OB 100 |
Number of asynchronous error OBs | 7; OB 80, 81, 82, 85, 87, 121, 122 |
Nesting depth |
per priority class | 8 |
Counters, timers and their retentivity |
S7 counter |
Number | 64 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 63 |
Counting range |
— lower limit | 0 |
— upper limit | 999 |
S7 times |
Number | 128 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 127 |
Time range |
— lower limit | 10 ms |
— upper limit | 9 990 s |
Data areas and their retentivity |
Flag |
Number, max. | 256 byte |
Retentivity available | Yes |
of which retentive with battery | 0 to 2047 |
of which retentive without battery | 0 to 2047 |
Address area |
I/O address area |
Inputs | 1 kbyte |
Outputs | 1 kbyte |
Process image |
Inputs | 128 byte |
Outputs | 128 byte |
Hardware configuration |
connectable programming devices/PCs | SIMATIC PG/PC, standard PC |
Number of modules per system, max. | 8 |
Number of modules per DP slave interface, max. | 32; 122 byte address space per DP station |
Interface modules |
Interface module IM 360 integrated | Yes |
Number of DP masters |
via CP | 1; CP 342-5 |
Number of operable FMs and CPs (recommended) |
FM | 8 |
CP, PtP | 4 |
CP, LAN | 2 |
Expansion modules |
Analog inputs/outputs, max. | 192 |
Digital inputs/outputs, max. | 768 |
Number of expansion modules, max. | 24 |
Rack |
Number of lines, max. | 3 |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
Digital inputs |
Number of digital inputs | 16 |
Input voltage |
Rated value (DC) | 24 V |
for signal "0" | -3 to +5V |
for signal "1" | +11 to +30V |
Input current |
for signal "1", typ. | 11.5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", max. | 4.8 ms; typically 3 ms |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Digital outputs |
Number of digital outputs | 16 |
Short-circuit protection | Yes; Clocked electronically |
Limitation of inductive shutdown voltage to | 48 V |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Output voltage |
for signal "1", min. | L+ (-0.8 V) |
Output current |
for signal "1" rated value | 0.5 A |
for signal "1" minimum load current | 5 mA |
for signal "0" residual current, max. | 0.5 mA |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
Total current of the outputs (per group) |
all mounting positions |
— up to 20 °C, max. | 4 A |
— up to 40 °C, max. | 2 A |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Universal inputs |
Number of universal inputs | 4 |
usable as | UI4: Digital/alarm input 24 V DC; UI1, UI2: additional up/down counter; UI3: additional frequency/period duration counter |
Input voltage |
Rated value (DC) | 24 V |
for signal "0" | -3 to +5V |
for signal "1" | +11 to +30V |
Input current |
for signal "1" | typ. 11.5 mA |
Cable length |
shielded, max. | 1 000 m |
Analog inputs |
Number of analog inputs | 4 |
permissible input voltage for voltage input (destruction limit), max. | 30 V |
permissible input current for current input (destruction limit), max. | 30 mA |
Cycle time (all channels), typ. | 2 ms |
Input ranges |
Voltage | Yes |
Current | Yes |
Input ranges (rated values), voltages |
-10 V to +10 V | Yes |
Input resistance (-10 V to +10 V) | 50 kΩ |
Input ranges (rated values), currents |
-20 mA to +20 mA | Yes |
Input resistance (-20 mA to +20 mA) | 105.5 Ω |
4 mA to 20 mA | Yes |
Input resistance (4 mA to 20 mA) | 105.5 kΩ |
Analog outputs |
Number of analog outputs | 4 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 25 mA |
Current output, no-load voltage, max. | 16 V; ± |
Cycle time (all channels) max. | 4 ms; typ. 2 ms |
Output ranges, voltage |
-10 V to +10 V | Yes |
Output ranges, current |
-20 mA to +20 mA | Yes |
4 mA to 20 mA | Yes |
Load impedance (in rated range of output) |
with voltage outputs, min. | 2 kΩ |
with voltage outputs, capacitive load, max. | 1 µF |
with current outputs, max. | 0.5 kΩ |
with current outputs, inductive load, max. | 1 mH |
Cable length |
shielded, max. | 200 m |
Analog value generation for the inputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 12 bit |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 12 bit |
Conversion time (per channel) | 0.5 ms |
Settling time |
for resistive load | 0.1 ms |
for capacitive load | 3.3 ms |
for inductive load | 0.5 ms |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 2 mA |
Errors/accuracies |
Operational error limit in overall temperature range |
Voltage, relative to input range, (+/-) | 0.8 % |
Current, relative to input range, (+/-) | 0.8 % |
Voltage, relative to output range, (+/-) | 0.8 % |
Current, relative to output range, (+/-) | 1 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input range, (+/-) | 0.6 % |
Current, relative to input range, (+/-) | 0.6 % |
Voltage, relative to output range, (+/-) | 0.5 % |
Current, relative to output range, (+/-) | 0.6 % |
Interfaces |
Number of printer interfaces | 1; RS 232 |
MPI |
Cable length, max. | 9 100 m; without repeaters 50 m; with 2 repeaters: 1100 m; with 10 repeaters in series: 9100 m; via fiber optic cable: 23.8 km (with star hubs or OLMs) |
1. Interface |
Protocols |
MPI | Yes; occupies 2 nodes per device (1 x CPU, 1 x OP) |
MPI |
Number of nodes, max. | 32; PG/PC, OP, C7, S7-300/400, M7 |
Transmission rate, max. | 187.5 kbit/s |
Communication functions |
S7 communication |
S7 extended communication | Yes; Server |
S5 compatible communication |
supported | Yes |
Standard communication (FMS) |
supported | Yes |
Number of connections |
overall | |
— of which dynamic | 8 |
— of which static | 4 |
Interrupts/diagnostics/status information |
Diagnostics function | Yes; C7-CPU |
Substitute values connectable | Yes; Parameterizable |
Alarms |
Alarm cycle | Yes; Parameterizable |
Diagnostic alarm | Yes; Measurement overrange, wire break detection at 4 to 20 mA by means of software; parameterizable for parameter errors |
Counter |
Number of counter inputs | 3; UE1, UE2, UE3 |
Principle | Counting of edges |
Counting range, description | UI1, UI2: up: 0 to 65535, down: 65535 to 0; UI3: up: 0 to 16777215, down: 16777215 to 0 |
Counter frequency, max. | 10 kHz |
Counting alarm backward counter | on reaching "0" |
Counting alarm forward counter | on reaching limit value |
Enable | In the program |
Limit value (setpoint) default | one counter per value |
External gate counters |
Number of external gate counters | 3 |
Principle | Counting of edges within a gate time via external pin |
Counting range | UE1, UE2: 0 to 65535; UE3: 0 to 16777215 |
Frequency counter |
Number | 1; UI3 |
Principle | Counting of pulses within a time period |
Gate width, adjustable | Yes |
Gate width | 0.1 / 1 / 10 s |
Counting range | 0 to 16777215 |
Cycle duration counter |
Number | 1; UI3 |
Cycle duration, max. | 8.38 s; or 0.12 Hz |
Principle | Counting of fixed time units between two positive edges |
Counting range, lower limit | 0 |
Counting range, upper limit | 16 777 214 |
Potential separation |
Potential separation digital inputs |
Potential separation digital inputs | Yes; Optocoupler |
between the channels, in groups of | 16 |
Potential separation digital outputs |
Potential separation digital outputs | Yes; Optocoupler |
between the channels, in groups of | 2 |
Potential separation analog inputs |
Potential separation analog inputs | Yes; shared with AO |
Potential separation analog outputs |
Potential separation analog outputs | Yes; Shared with IO |
Potential separation channels |
Potential separation universal inputs | No |
Isolation |
Isolation tested with | 500 V DC |
EMC |
EMC interference immunity | Noise immunity: IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4, IEC 1000-4-6, EN 50140 |
Emission of radio interference acc. to EN 55 022 |
Interference emission acc. to EN 55022, class A | Yes; Noise emission: Class A / EN 55022; conducted interference: IEC 1000-4-4, IEC 1000-4-5 |
Degree and class of protection |
Degree of protection acc. to EN 60529 | |
IP20 | Yes; Housing |
IP65 | Yes; Front |
Standards, approvals, certificates |
CSA approval | Yes; to Standard C22.2 number 142 |
UL approval | Yes; UL 508 |
FM approval | Yes; FM-Standards No. 3611, 3600, 3810 Class I, Division 2, Group A, B, C, D |
developed in accordance with IEC 61131 | Yes; EN 61131-2 (IEC 1131-2) |
DIN/ISO 9001 | Yes |
Ambient conditions |
Ambient temperature during operation |
45 degree installation, min. | 0 °C |
45 degree installation, max. | 45 °C |
vertical installation, min. | 0 °C |
vertical installation, max. | 50 °C |
Air pressure acc. to IEC 60068-2-13 |
permissible range, lower limit | 795 hPa |
permissible range, upper limit | 1 080 hPa |
Relative humidity |
Operation, min. | 5 % |
Operation, max. | 95 %; at 25 °C (no condensation), tested to DIN IEC 60068-2-3 |
Vibrations |
Operation, tested according to IEC 60068-2-6 | Yes; IEC 60068-2-6; 10 Hz to 58 Hz; (constant amplitude 0.075 mm); 58 Hz to 500 Hz; (constant acceleration 9.8 m/s²) |
Shock testing |
tested according to IEC 60068-2-29 | Yes; IEC 68, Part 2-29 half-sine: 100 m/s² (10 g), 16 ms, 100 shocks |
Configuration |
Configuration software |
STEP 7 | Yes |
STEP 7 Lite | Yes |
ProTool | Yes |
ProTool/Lite | Yes |
ProTool/Pro | Yes |
Programming |
Command set | see instruction list |
Nesting levels | 8 |
Program organization | Linear, structured |
System functions (SFC) | see instruction list |
Programming language |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes |
— CFC | Yes |
— GRAPH | Yes |
— HiGraph® | Yes |
Software libraries |
— Process diagnostics | Yes; C7-CPU |
— Software controller | Yes; 16 circles |
Know-how protection |
User program protection/password protection | Yes |
Cycle time monitoring |
lower limit | 1 ms |
upper limit | 6 000 ms |
adjustable | Yes |
preset | 150 ms |
Languages |
Online languages |
Number of online/runtime languages | 3 |
Dimensions |
Width | 240 mm |
Height | 168 mm |
Depth | 89.4 mm |
Mounting cutout, width | 231 mm |
Mounting cutout, height | 159 mm |
Weights |
Weight, approx. | 1 900 g |
last modified: | 03/13/2019 |