6ES7332-5RD00-0AB0
SIMATIC S7,SM 332 ANALOG OUTPUT

From SIEMENS

SIMATIC S7, analog output SM 332, isolated, 4 AA; 0/4 to 20 mA, 20-pole, for signals from the hazardous area, diagnostics-capable, PTB tested
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.200 mA
from backplane bus 5 V DC, max.80 mA
Power loss
Power loss, typ.4 W
Analog outputs
Number of analog outputs4
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.70 mA
Current output, no-load voltage, max.14 V
Output ranges, current
0 to 20 mAYes
4 mA to 20 mAYes
Connection of actuators
for current output two-wire connectionYes
Load impedance (in rated range of output)
with current outputs, max.500 Ω
Cable length
shielded, max.200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.15 bit
Basic conversion time (ms)2.5 ms
Errors/accuracies
Operational error limit in overall temperature range
Current, relative to output range, (+/-)0.55 %
Basic error limit (operational limit at 25 °C)
Current, relative to output range, (+/-)0.2 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Diagnostic messages
Diagnostic information readableYes
OverrangeYes
Wire-break in actuator cableYes
Diagnostics indication LED
Group error SF (red)Yes
Channel fault indicator F (red)Yes
Ex(i) characteristics
Module for Ex(i) protectionYes
Maximum values of output circuits (per channel)
Co (permissible external capacity), max.850 nF
Io (short-circuit current), max.70 mA
Lo (permissible external inductivity), max.6.6 mH
Po (power of load), max.440 mW
Uo (output no-load voltage), max.14 V
Potential separation
Potential separation analog outputs
Potential separation analog outputsYes
Permissible potential difference
between the outputs (UCM)60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
Between the outputs and MANA (UCM)60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
Standards, approvals, certificates
Use in hazardous areas
Type of protection acc. to EN 50020 (CENELEC)[EEx ib] IIC
Type of protection acc. to FMClass I, Division 2, Group A, B, C, D T4
Test number PTBEx-96.D.2026X
Ambient conditions
Ambient temperature during operation
max.60 °C
Connection method
required front connector20-pin
Weights
Weight, approx.280 g