6ES7321-7BH00-0AB0 SM 321, 16*DC 24V, with interrupts
From SIEMENS
SIMATIC S7-300, DIGITAL INPUT SM 321, OPTICALLY ISOLATED, 16 DI, DC 24V, 20 PIN, PROCESS INTERRUPT, DIAGNOSTICS | ||
Supply voltage | ||
Load voltage L+ | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
from load voltage L+ (without load), max. | 40 mA | |
from backplane bus 5 V DC, max. | 55 mA | |
Power loss | ||
Power loss, typ. | 4 W | |
Digital inputs | ||
Number of digital inputs | 16 | |
Number of simultaneously controllable inputs | ||
all mounting positions | ||
— up to 40 °C, max. | 16 | |
— up to 60 °C, max. | 16 | |
Input voltage | ||
Rated value (DC) | 24 V | |
for signal "0" | -30 to +5V | |
for signal "1" | 13 to 30V | |
Input current | ||
for signal "1", typ. | 7 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; 0.1 / 0.5 / 3 / 15 / 20 ms | |
Cable length | ||
shielded, max. | 1 000 m | |
unshielded, max. | 600 m | |
Encoder | ||
Connectable encoders | ||
2-wire sensor | Yes | |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes; internal/ external fault | |
Alarms | ||
Diagnostic alarm | Yes | |
Hardware interrupt | Yes | |
Potential separation | ||
Potential separation digital inputs | ||
between the channels, in groups of | 16 | |
between the channels and backplane bus | Yes; Optocoupler | |
Isolation | ||
Isolation tested with | 500 V DC | |
Connection method | ||
required front connector | 20-pin | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights | ||
Weight, approx. | 200 g | |
last modified: | 03/13/2019 |