| SIMATIC S7-300, CPU 314 CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 64 KBYTE WORKING MEMORY MICRO MEMORY CARD NECESSARY |
General information |
HW functional status | 01 |
Firmware version | V2.0.0 |
Engineering with |
Programming package | STEP 7 V5.2 + SP1 or higher with HW update |
Supply voltage |
Rated value (DC) | |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
external protection for power supply lines (recommendation) | 2 A min. |
Input current |
Current consumption (rated value) | 0.6 A |
Current consumption (in no-load operation), typ. | 60 mA |
Inrush current, typ. | 2.5 A |
I²t | 0.5 A²·s |
Power loss |
Power loss, typ. | 2.5 W |
Memory |
Work memory |
integrated | 64 kbyte |
expandable | No |
Load memory |
Plug-in (MMC) | Yes |
Plug-in (MMC), max. | 8 Mbyte |
Data management on MMC (after last programming), min. | 10 y |
Backup |
present | Yes; Guaranteed by MMC (maintenance-free) |
without battery | Yes; Program and data |
Battery |
Backup battery |
Backup time, max. | 10 y; At 40 °C ambient temperature |
CPU processing times |
for bit operations, typ. | 0.1 µs |
for bit operations, max. | 0.2 µs |
for word operations, typ. | 0.2 µs |
for fixed point arithmetic, typ. | 2 µs |
for floating point arithmetic, typ. | 3 µs |
CPU-blocks |
Number of blocks (total) | 1 024; (DBs, FCs, FBs OBs, SDBs); the maximum number of loadable blocks can be reduced by the MMC being used. |
DB |
Number, max. | 511; Number range: 1 to 511 |
Size, max. | 16 kbyte |
FB |
Number, max. | 512; Number range: 0 to 2047 |
Size, max. | 16 kbyte |
FC |
Number, max. | 512; Number range: 0 to 2047 |
Size, max. | 16 kbyte |
OB |
Number, max. | see instruction list |
Size, max. | 16 kbyte |
Number of free cycle OBs | 1; OB 1 |
Number of time alarm OBs | 1; OB 10 |
Number of delay alarm OBs | 1; OB 20 |
Number of cyclic interrupt OBs | 1; OB 35 |
Number of process alarm OBs | 1; OB 40 |
Number of startup OBs | 1; OB 100 |
Number of asynchronous error OBs | 1; OB 80 |
Number of synchronous error OBs | 2; OB 121, 122 |
Nesting depth |
per priority class | 8 |
additional within an error OB | 4 |
Counters, timers and their retentivity |
S7 counter |
Number | 256 |
Retentivity |
— adjustable | Yes |
— preset | Z 0 to Z 7 |
Counting range |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
S7 times |
Number | 256 |
Retentivity |
— adjustable | Yes |
— preset | No retentivity |
Time range |
— lower limit | 10 ms |
— upper limit | 9 990 s |
IEC timer |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area in total | All (incl. memory bits, times, counters) |
Flag |
Number, max. | 256 byte |
Retentivity available | Yes; MB 0 to MB 255 |
Retentivity preset | MB 0 to MB 15 |
Number of clock memories | 8; 1 memory byte |
Data blocks |
Retentivity adjustable | No |
Retentivity preset | Yes |
Local data |
per priority class, max. | 510 byte |
Address area |
I/O address area |
Inputs | 1 kbyte |
Outputs | 1 kbyte |
Process image |
Inputs | 128 byte |
Outputs | 128 byte |
Digital channels |
Inputs | 1 024 |
— of which central | 1 024 |
Outputs | 1 024 |
— of which central | 1 024 |
Analog channels |
Inputs | 256 |
— of which central | 256 |
Outputs | 256 |
— of which central | 256 |
Hardware configuration |
Number of DP masters |
integrated | 0 |
via CP | 4 |
Number of operable FMs and CPs (recommended) |
FM | 8 |
CP, PtP | 8 |
CP, LAN | 10 |
Rack |
Racks, max. | 4 |
Modules per rack, max. | 8 |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
retentive and synchronizable | Yes |
Backup time | 6 wk; At 40 °C ambient temperature |
Deviation per day, max. | 10 s |
Operating hours counter |
Number | 1 |
Number/Number range | 0 |
Range of values | 0 to 2^31 hours (when using SFC 101) |
Granularity | 1 h |
retentive | Yes; Must be restarted at each restart |
Clock synchronization |
supported | Yes |
to MPI, master | Yes |
to MPI, slave | Yes |
in AS, master | Yes |
Analog inputs |
integrated channels (AI) | 0 |
Analog outputs |
integrated channels (AO) | 0 |
1. Interface |
Interface type | Integrated RS 485 interface |
Physics | RS 485 |
Isolated | No |
Power supply to interface (15 to 30 V DC), max. | 200 mA |
Protocols |
MPI | Yes |
PROFIBUS DP master | No |
PROFIBUS DP slave | No |
Point-to-point connection | No |
MPI |
Number of connections | 12 |
Transmission rate, max. | 187.5 kbit/s |
Services |
— PG/OP communication | Yes |
— Routing | No |
— Global data communication | Yes |
— S7 basic communication | Yes |
— S7 communication | Yes |
— S7 communication, as client | No |
— S7 communication, as server | Yes |
Communication functions |
PG/OP communication | Yes |
Global data communication |
supported | Yes |
Number of GD loops, max. | 4 |
Number of GD packets, max. | 4 |
Number of GD packets, transmitter, max. | 4 |
Number of GD packets, receiver, max. | 4 |
Size of GD packets, max. | 22 byte |
Size of GD packet (of which consistent), max. | 22 byte |
S7 basic communication |
supported | Yes |
User data per job, max. | 76 byte |
User data per job (of which consistent), max. | 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication |
supported | Yes |
as server | Yes |
as client | Yes; Via CP and loadable FB |
User data per job, max. | 180 byte; With PUT/GET |
User data per job (of which consistent), max. | 64 byte |
S5 compatible communication |
supported | Yes; via CP and loadable FC |
Number of connections |
overall | 12 |
usable for PG communication | 11 |
— reserved for PG communication | 1 |
— adjustable for PG communication, min. | 1 |
— adjustable for PG communication, max. | 11 |
usable for OP communication | 11 |
— reserved for OP communication | 1 |
— adjustable for OP communication, min. | 1 |
— adjustable for OP communication, max. | 11 |
usable for S7 basic communication | 8 |
— reserved for S7 basic communication | 8 |
— adjustable for S7 basic communication, min. | 0 |
— adjustable for S7 basic communication, max. | 8 |
S7 message functions |
Number of login stations for message functions, max. | 12; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages | Yes |
simultaneously active Alarm-S blocks, max. | 40 |
Test commissioning functions |
Status block | Yes |
Single step | Yes |
Number of breakpoints | 2 |
Status/control |
Status/control variable | Yes |
Variables | Inputs, outputs, memory bits, DB, times, counters |
Number of variables, max. | 30 |
— of which status variables, max. | 30 |
— of which control variables, max. | 14 |
Forcing |
Forcing | Yes |
Forcing, variables | Inputs, outputs |
Number of variables, max. | 10 |
Diagnostic buffer |
present | Yes |
Number of entries, max. | 100 |
— adjustable | No |
Configuration |
Configuration software |
STEP 7 | Yes; V5.2 SP1 or higher with HW update |
Programming |
Command set | see instruction list |
Nesting levels | 8 |
System functions (SFC) | see instruction list |
System function blocks (SFB) | see instruction list |
Programming language |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes |
— CFC | Yes |
— GRAPH | Yes |
— HiGraph® | Yes |
Know-how protection |
User program protection/password protection | Yes |
Dimensions |
Width | 40 mm |
Height | 125 mm |
Depth | 130 mm |
Weights |
Weight, approx. | 280 g |
last modified: | 03/13/2019 |