6ES7136-6DC00-0CA0
ET 200SP, F-DQ 8x 24VDC/0.5A PP

From SIEMENS

SIMATIC DP, Electronics module ET 200SP, F-DQ 8XDC 24V0.5A PP, 15 mm width, up to PL E (ISO 13849) up to SIL 3 (IEC 61508)
General information
Product type designationF-DQ 8x24 V DC/0.5 A PP HF
Firmware version
FW update possibleYes
usable BaseUnitsBU type A0
Color code for module-specific color identification plateCC02
Product function
I&M dataYes; I&M0 to I&M3
Engineering with
STEP 7 TIA Portal configurable/integrated as of versionV14 SP1 with HSP 202
STEP 7 configurable/integrated as of versionV5.5 SP4 HF5
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)75 mA; without load
Current consumption, max.21 mA; From the backplane bus
Output voltage
Rated value (DC)24 V
Power
Power available from the backplane bus70 mW
Power loss
Power loss, typ.3 W
Address area
Address space per module
Inputs6 byte; 5 bytes non-RIOforFA; 6 bytes RIOforFA
Outputs6 byte; 5 bytes non-RIOforFA; 6 bytes RIOforFA
Hardware configuration
Automatic encoding
Electronic coding element type FYes
Digital outputs
Number of digital outputs8
Digital outputs, parameterizableYes
Short-circuit protectionYes
Response threshold, typ.Min. 0.7 A
Open-circuit detectionNo
Limitation of inductive shutdown voltage toTyp. -39 V
Controlling a digital inputYes
Switching capacity of the outputs
with resistive load, max.0.5 A
on lamp load, max.2 W
Load resistance range
lower limit48 Ω
upper limit12 000 Ω
Output voltage
for signal "1", min.24 V; L+ (-0.5 V)
Output current
for signal "1" rated value0.5 A
for signal "0" residual current, max.0.5 mA
Switching frequency
with resistive load, max.30 Hz; Symmetrical
with inductive load, max.0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical
with capacitive load, max.2 Hz; Symmetrical
on lamp load, max.10 Hz; Symmetrical
Total current of the outputs
Current per channel, max.0.5 A; Note derating data in the manual
Current per module, max.3 A; Note derating data in the manual
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max.3 A
— up to 50 °C, max.2.5 A
— up to 60 °C, max.2 A
vertical installation
— up to 50 °C, max.2 A
Cable length
shielded, max.100 m
unshielded, max.100 m
Interrupts/diagnostics/status information
Diagnostics functionYes, "Alarms/diagnostic messages" section in the manual
Substitute values connectableNo
Alarms
Diagnostic alarmYes
Diagnostics indication LED
RUN LEDYes; Green LED
ERROR LEDYes; Red LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; Green LED
for channel diagnosticsYes; Red LED
for module diagnosticsYes; green/red DIAG LED
Potential separation
Potential separation channels
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsYes
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1PLe
SIL acc. to IEC 61508SIL 3
Probability of failure (for service life of 20 years and repair time of 100 hours)
— Low demand mode: PFDavg in accordance with SIL3< 6.00E-05
— High demand/continuous mode: PFH in accordance with SIL3< 2.00E-09 1/h
Ambient conditions
Ambient temperature during operation
horizontal installation, min.0 °C
horizontal installation, max.60 °C
vertical installation, min.0 °C
vertical installation, max.50 °C
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.48 g
last modified:03/08/2019