| SIMATIC DP, ELECTRONIC MODULE ET 200SP, F-AI 4xI(0)4..20mA HF FAILSAFE ANALOG INPUTS up to PL E (ISO 13849) up to SIL 3 (IEC 61508) |
General information |
Product type designation | F-AI 4xI 0(4) ... 20 mA 2/4-wire HF |
Firmware version | |
FW update possible | Yes |
usable BaseUnits | BU type A0, A1 |
Color code for module-specific color identification plate | CC00 |
Product function |
I&M data | Yes; I&M0 to I&M3 |
Engineering with |
STEP 7 TIA Portal configurable/integrated as of version | V15 with HSP 203 |
CiR – Configuration in RUN |
Reparameterization possible in RUN | No |
Calibration possible in RUN | No |
Supply voltage |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
Current consumption (rated value) | 0.38 A |
Current consumption, max. | 0.4 A |
Encoder supply |
24 V encoder supply |
24 V | Yes; min. L+ (-1.5 V) |
Short-circuit protection | Yes |
Output current, max. | 300 mA; total current of all encoders/channels |
Power |
Power available from the backplane bus | 70 mW |
Power loss |
Power loss, typ. | 2 W |
Address area |
Address space per module |
Inputs | 14 byte; S7-300/400F CPU, 13 byte |
Outputs | 5 byte; S7-300/400F CPU, 4 byte |
Hardware configuration |
Automatic encoding | |
Electronic coding element type F | Yes |
Analog inputs |
Number of analog inputs | 4 |
For current measurement | 4 |
permissible input current for current input (destruction limit), max. | 35 mA |
Input ranges (rated values), currents |
0 to 20 mA | Yes |
Input resistance (0 to 20 mA) | 125 Ω |
4 mA to 20 mA | Yes |
Input resistance (4 mA to 20 mA) | 125 Ω |
Cable length |
shielded, max. | 1 000 m |
Analog value generation for the inputs |
Measurement principle | Sigma Delta |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit |
Integration time, parameterizable | Yes |
Integration time (ms) | 20 / 16,667 |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Smoothing of measured values |
Number of smoothing levels | 7 |
parameterizable | Yes |
Step: None | Yes; 1x conversion cycle time |
Step: low | Yes; 2x / 4x conversion cycle time |
Step: Medium | Yes; 8x / 16x conversion cycle time |
Step: High | Yes; 32x / 64x conversion cycle time |
Encoder |
Connection of signal encoders |
for current measurement as 2-wire transducer | Yes |
— Burden of 2-wire transmitter, max. | 650 Ω |
for current measurement as 4-wire transducer | Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.1 % |
Temperature error (relative to input range), (+/-) | 0.023 %/K |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.1 % |
Operational error limit in overall temperature range |
Current, relative to input range, (+/-) | 2 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to input range, (+/-) | 0.1 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 40 dB |
Common mode interference, min. | 70 dB |
Interrupts/diagnostics/status information |
Diagnostics function | Yes, "Alarms/diagnostic messages" section in the manual |
Alarms |
Diagnostic alarm | Yes |
Limit value alarm | Yes |
Diagnostic messages |
Monitoring the supply voltage | Yes |
Wire-break | Yes; Measuring range 4 to 20 mA only |
Short-circuit | Yes |
Diagnostics indication LED |
RUN LED | Yes; Green LED |
ERROR LED | Yes; Red LED |
Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Channel status display | Yes; Green LED |
for channel diagnostics | Yes; Red LED |
for module diagnostics | Yes; Green/red LED |
Potential separation |
Potential separation channels |
between the channels | No |
between the channels and backplane bus | Yes |
between the channels and the power supply of the electronics | Yes |
Permissible potential difference |
between the inputs (UCM) | 10 Vpp |
Isolation |
Isolation tested with | 707 V DC (type test) |
Ambient conditions |
Ambient temperature during operation |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C |
vertical installation, min. | 0 °C |
vertical installation, max. | 50 °C |
Dimensions |
Width | 15 mm |
Height | 73 mm |
Depth | 58 mm |
Weights |
Weight, approx. | 48 g |
last modified: | 03/13/2019 |