6ES7135-0HF01-0XB0
ET200B, EL-MOD., 4AO, 0/4-20MA, +/-10V

From SIEMENS

*** SPARE PART*** SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S
General information
Usable terminal blockTB8
Supply voltage
Rated value (DC)24 V; Value at t < 0.5 s: 35 V
permissible range, lower limit (DC)18.5 V
permissible range, upper limit (DC)30.2 V
Input current
Current consumption, max.200 mA; Logic
Power loss
Power loss, typ.2.4 W
Analog outputs
Number of analog outputs4
Voltage output, short-circuit protectionYes; Electronic; max. 1 output in parallel
Voltage output, short-circuit current, max.25 mA
Current output, no-load voltage, max.18 V
Output ranges, voltage
0 to 10 VYes
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes
for voltage output four-wire connectionYes
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.300 Ω
with current outputs, inductive load, max.1 mH
Cable length
shielded, max.100 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.11 bit; Two's complement
Conversion time (per channel)1 ms
Settling time
for resistive load0.1 ms
for capacitive load3.3 ms
for inductive load0.5 ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.05 %
Linearity error (relative to output range), (+/-)0.05 %
Temperature error (relative to output range), (+/-)0.02 %/K
Crosstalk between the outputs, min.40 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0.05 %
Current, relative to output range, (+/-)1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.2 %
Current, relative to output range, (+/-)0.3 %
Interfaces
PROFIBUS DP
Transmission rate, max.12 Mbit/s
Protocols
Bus protocol/transmission protocolPROFIBUS DP
Interrupts/diagnostics/status information
Alarms
Diagnostic alarmYes; Parameterizable
Diagnostics indication LED
RUN LEDYes
Bus fault BF (red)Yes
Potential separation
between electronic block and PROFIBUS DPYes
Potential separation analog outputs
Potential separation analog outputsNo
Degree and class of protection
Degree of protection acc. to EN 60529IP20
Ambient conditions
Ambient temperature during operation
horizontal installation, min.0 °C
horizontal installation, max.60 °C; 40°C for other mountings
Air pressure acc. to IEC 60068-2-13
permissible range, lower limit795 hPa
permissible range, upper limit1 080 hPa
Relative humidity
Operation, min.15 %
Operation, max.95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, tested according to IEC 60068-2-6Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock testing
tested according to IEC 60068-2-27Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Connection method
Design of electrical connection for the inputs and outputsScrew-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width160 mm; EB and TB
Height130 mm; EB and TB
Depth60 mm; EB and TB
Weights
Weight, approx.550 g; EB and TB
last modified:03/13/2019