| SIMATIC DP, electronics module for ET200iSP, 4 AI, RTD, for connection of resistance thermometers Pt100/NI100 |
Input current |
Current consumption, typ. | 19 mA |
from supply voltage L+, max. | 22 mA |
Power loss |
Power loss, typ. | 0.4 W |
Analog inputs |
Number of analog inputs | 4 |
Cycle time (all channels) max. | 320 ms; 66 ms basic conversion time x 4 channels with interference frequency suppression 60 Hz, 80 ms basic conversion time x 4 channels with interference frequency suppression 50 Hz |
Technical unit for temperature measurement adjustable | Yes |
Input ranges (rated values), resistance thermometer |
Ni 100 | Yes |
Input resistance (Ni 100) | 2 000 kΩ |
Pt 100 | Yes |
Input resistance (Pt 100) | 2 000 kΩ |
Input ranges (rated values), resistors |
0 to 600 ohms | Yes; Also 1 000 ohms |
Input resistance (0 to 600 ohms) | 1 000 kΩ |
Characteristic linearization |
parameterizable | Yes |
— for resistance thermometer | Yes |
Cable length |
shielded, max. | 500 m |
Analog value generation for the inputs |
Measurement principle | integrating (Sigma-Delta) |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit |
Integration time, parameterizable | Yes |
Basic conversion time, including integration time (ms) | 80 ms at 50 Hz; 66 ms at 60 Hz |
— additional conversion time for wire-break monitoring | 5 ms |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Smoothing of measured values |
parameterizable | Yes; in 4 stages |
Step: None | Yes; 1x cycle time |
Step: low | Yes; 4x cycle time |
Step: Medium | Yes; 32x cycle time |
Step: High | Yes; 64x cycle time |
Encoder |
Connection of signal encoders |
for resistance measurement with two-wire connection | Yes |
for resistance measurement with three-wire connection | Yes |
for resistance measurement with four-wire connection | Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.015 % |
Temperature error (relative to input range), (+/-) | 0.02 %/K |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.01 % |
Operational error limit in overall temperature range |
Resistance thermometer, relative to input range, (+/-) | 0.15 %; Applies to resistances standard ±0.8 K, climatic ±0.3 K |
Basic error limit (operational limit at 25 °C) |
Resistance thermometer, relative to input range, (+/-) | 0.1 %; Applies to resistances standard ±0.5 K, climatic ±0.2 K |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
Common mode interference, min. | 90 dB |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm | Yes |
Limit value alarm | Yes |
Diagnostic messages |
Diagnostic information readable | Yes |
Wire-break | Yes |
Short-circuit | Yes |
Group error | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Potential separation |
Potential separation analog inputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | Yes; Channels and power bus |
Standards, approvals, certificates |
CE mark | Yes |
Highest safety class achievable in safety mode |
Performance level according to ISO 13849-1 | none |
SIL acc. to IEC 61508 | No |
Use in hazardous areas |
Type of protection acc. to EN 50020 (CENELEC) | II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I |
Type of protection acc. to KEMA | 04 ATEX 1247 |
Dimensions |
Width | 30 mm |
Height | 129 mm |
Depth | 136.5 mm |
Weights |
Weight, approx. | 230 g |