| SIMATIC DP, Electronics module for ET 200S, 4 AI TC, +/-80 mV; 15 mm width, 15 bit+sign with SF LED (group fault) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 30 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Power loss |
Power loss, typ. | 0.6 W |
Address area |
Address space per module |
Address space per module, max. | 8 byte |
Analog inputs |
Number of analog inputs | 4 |
permissible input voltage for voltage input (destruction limit), max. | 10 V; Permanent |
Cycle time (all channels) max. | Number of active channels per module x basic conversion time |
Technical unit for temperature measurement adjustable | No; Celsius |
Input ranges (rated values), voltages |
-80 mV to +80 mV | Yes |
Input resistance (-80 mV to +80 mV) | 1 MΩ |
Input ranges (rated values), thermocouples |
Type B | Yes |
Input resistance (Type B) | 1 MΩ |
Type E | Yes |
Input resistance (Type E) | 1 MΩ |
Type J | Yes |
Input resistance (type J) | 1 MΩ |
Type K | Yes |
Input resistance (Type K) | 1 MΩ |
Type L | Yes |
Input resistance (Type L) | 1 MΩ |
Type N | Yes |
Input resistance (Type N) | 1 MΩ |
Type R | Yes |
Input resistance (Type R) | 1 MΩ |
Type S | Yes |
Input resistance (Type S) | 1 MΩ |
Type T | Yes |
Input resistance (Type T) | 1 MΩ |
Thermocouple (TC) |
Temperature compensation |
— internal temperature compensation | Not possible |
— external temperature compensation with compensations socket | Yes; possible, one external compensating box per channel |
Characteristic linearization |
parameterizable | Yes; Type B, E, J, K, L, N, R, S, T to IEC 584 |
Cable length |
shielded, max. | 50 m |
Analog value generation for the inputs |
Measurement principle | integrating |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit; 15 bit + sign |
Integration time, parameterizable | Yes |
Integration time (ms) | 16,7 / 20 ms |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Conversion time (per channel) | 65 ms; 55 / 65 ms (additional 20 ms on activated wire-break test) |
Smoothing of measured values |
parameterizable | Yes; In four stages by means of digital filtering |
Step: None | Yes; 1x cycle time |
Step: low | Yes; 4x cycle time |
Step: Medium | Yes; 32x cycle time |
Step: High | Yes; 64x cycle time |
Encoder |
Connection of signal encoders |
for voltage measurement | Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.01 % |
Temperature error (relative to input range), (+/-) | 0.005 %/K |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range |
Voltage, relative to input range, (+/-) | 0.6 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input range, (+/-) | 0.4 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
Common mode interference (USS < 2.5 V) , min. | 90 dB |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Diagnostic messages |
Diagnostic information readable | Yes |
Wire-break | Yes; A break in the wire is only detected for thermocouples |
Group error | Yes |
Overflow/underflow | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 4 byte |
Diagnostics wire break | Disable / enable (wire break is detected only in thermocouples) |
Measurement type/range | Deactivated/ ±80 mV/ TC-EL Type T (Cu-CuNi)/ TC-EL Type K (NiCr-Ni)/ TC-EL Type B (PtRh-PtRh)/ TC-EL Type c (Wer-Wer) TC-EL Type N (NiCrSi-NiSi)/ TC-EL Type E (NiCr-CuNi)/ TC-EL Type R (PtRh-Pt)/ TC-EL Type S (PtRh-Pt)/ TC-EL Type J (Fe-Cu-Ni)/ TC |
Group diagnostics | Disable / enable |
Overflow/underflow | Disable / enable |
Comparison point | none / RTD |
Comparison point number | None / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 |
Potential separation |
Potential separation analog inputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | Yes |
Permissible potential difference |
Between the inputs and MANA (UCM) | 2 V AC PP |
between MANA and M internally (UISO) | 75 V DC/60 V AC |
Isolation |
Isolation tested with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |
last modified: | 03/13/2019 |