| SIMATIC ET 200SP, Digital input module, DI 4x 120..230V AC Standard, type 3 (IEC 61131), Packing unit: 1 piece, fits to BU-type B1, Colour Code CC41, module diagnostics |
General information |
Product type designation | DI 4x120 … 230 V AC ST |
Firmware version | V0.0 |
FW update possible | No |
usable BaseUnits | BU type B1 |
Color code for module-specific color identification plate | CC41 |
Product function |
I&M data | Yes; I&M0 to I&M3 |
Engineering with |
STEP 7 TIA Portal configurable/integrated as of version | V14 |
STEP 7 configurable/integrated as of version | V5.5 SP3 |
PROFIBUS as of GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
PROFINET as of GSD version/GSD revision | GSDML V2.3 |
Operating mode |
DI | Yes |
Counter | No |
Oversampling | No |
MSI | No |
Supply voltage |
Rated value (AC) | 230 V |
Reverse polarity protection | No |
Input current |
Current consumption (rated value) | 10 mA |
Encoder supply |
Number of outputs | 4 |
Short-circuit protection | No; when using BU type B1, a fuse with 10 A tripping current must be provided |
Output current |
up to 60 °C, max. | 10 A |
Power loss |
Power loss, typ. | 1 W; Active power, load voltage 230 V, all inputs connected with 230 V, 50 Hz |
Address area |
Address space per module |
Inputs | 1 byte; + 1 byte for QI information |
Hardware configuration |
Automatic encoding | Yes |
Mechanical coding element | Yes |
Selection of BaseUnit for connection variants |
1-wire connection | BU type B1 |
2-wire connection | BU type B1 |
3-wire connection | BU type B1 |
4-wire connection | BU type B1 + potential distributor module |
Digital inputs |
Number of digital inputs | 4 |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
Input voltage |
Rated value (AC) | 230 V |
for signal "0" | 0V AC to 40V AC |
for signal "1" | 74 V AC to 264 V AC |
Input current |
for signal "1", typ. | 10.8 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable | No |
— at "0" to "1", min. | 1.5 ms |
— at "0" to "1", max. | 4 ms |
— at "1" to "0", min. | 10 ms |
— at "1" to "0", max. | 10 ms |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm | No |
Hardware interrupt | No |
Diagnostic messages |
Monitoring the supply voltage | No |
Wire-break | No |
Short-circuit | No |
Diagnostics indication LED |
Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Channel status display | Yes; Green LED |
for channel diagnostics | No |
for module diagnostics | Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
between the channels | No |
between the channels and backplane bus | Yes |
between the channels and the power supply of the electronics | No |
Isolation |
Isolation tested with | 2 545 V DC/2 s (routine test) |
Standards, approvals, certificates |
Suitable for safety functions | No |
Ambient conditions |
Altitude during operation relating to sea level |
Ambient air temperature-barometric pressure-altitude | On request: Ambient temperatures lower than 0 °C (without condensation) and/or installation altitudes greater than 2 000 m |
Dimensions |
Width | 20 mm |
Height | 73 mm |
Depth | 58 mm |
Weights |
Weight, approx. | 36 g |
last modified: | 03/08/2019 |