6EP1961-2BA21
SITOP PSE200U SELECTIVITY MODULE 10A

From SIEMENS

SITOP PSE200U SELECTIVITY MODULE 10A
SITOP PSE200U 10 A Selectivity module 4-channel input: 24 V DC/40 A output: 24 V DC/4x 10 A Level adjustable 3-10 A with common signaling contact
Input
Type of the power supply networkControlled DC voltage
Supply voltage / at DC / Rated value24 V
Input voltage / at DC22 ... 30 V
Overvoltage overload capability35 V
Input current / at rated input voltage 24 V / Rated value40 A
Output
Voltage curve / at outputcontrolled DC voltage
Formula for output voltageVin - approx. 0.2 V
Relative overall tolerance / of the voltage / NoteIn accordance with the supplying input voltage
Number of outputs4
Output current / up to 60 °C / per output / rated value10 A
Adjustable pick-up value current / of the current-dependent overload release3 ... 10 A
Type of response value settingvia potentiometer
Product feature / parallel switching of outputsNo
Product feature / bridging of equipmentsYes
Type of outputs connectionSimultaneous connection of all outputs after power up of the supply voltage > 20 V, delay time of 25 ms, 100 ms or adjustable "load optimised" via DIP switch for sequential connection
Efficiency
Efficiency in percent99 %
Power loss [W] / at rated output current / for rated value of the output current / typical10 W
Switch-off characteristic per output
Switching characteristic
of the excess currentIout = 1.0 ...1.5 x set value, switch-off after approx. 5 s
of the current limitationIout = 1.5 x set value, switch-off after typ. 100 ms
of the immediate switch-offIout > set value and Vin < 20 V, switch-off after approx. 0.5 ms
Design of the reset device/resetting mechanismvia sensor per output
Remote reset functionNon-electrically isolated 24 V input (signal level "high" at > 15 V)
Protection and monitoring
Fuse protection type / at input15 A per output (not accessible)
Display version / for normal operationThree-color LED per output: green LED for "Output switched through"; yellow LED for "Output switched off manually"; red LED for "Output switched off due to overcurrent"
Design of the switching contact / for signaling functionCommon signal contact (changeover contact, rating 0.1 A/24 V DC)
Safety
Galvanic isolation / between input and output at switch-offNo
Operating resource protection classClass III
Certificate of suitability
CE markingYes
as approval for USAUL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508, CSA C22.2 No. 107.1) File E197259
Standard / for safetyaccording to EN 60950-1 and EN 50178
Certificate of suitability / relating to ATEXIECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus Class I, Div. 2, Group ABCD, T4
Shipbuilding approvalDNV GL, ABS
Protection class IPIP20
EMC
Standard
for emitted interferenceEN 55022 Class B
for interference immunityEN 61000-6-2
Operating data
Ambient temperature
during operation-25 ... +60 °C
— Notewith natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Environmental category / acc. to IEC 60721Climate class 3K3, no condensation
Mechanics
Type of electrical connectionscrew-type terminals
at input+24 V: 2 screw terminals for 0.5 ... 16 mm²; 0 V: 2 screw terminals for 0.5 ... 4 mm²
at outputOutput 1 ... 4: 1 screw terminal each for 0.5 ... 4 mm²
for signaling contact3 screw terminals for 0.5 ... 4 mm²
for auxiliary contactsRemote reset: 1 screw terminal for 0.5 ... 4 mm²
Width / of the enclosure72 mm
Height / of the enclosure80 mm
Depth / of the enclosure72 mm
Installation width72 mm
Mounting height180 mm
Net weight0.2 kg
Mounting typeSnaps onto DIN rail EN 60715 35x7.5/15
Mechanical accessoriesDevice identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
MTBF / at 40 °C540 979 h
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)