6EP1433-2CA00
SITOP PSU300P 24 V/8 A, IP67

From SIEMENS

SITOP PSU300P 24 V/8 A, IP67
SITOP PSU300P 8 A Stabilized power supply Protection class IP67 input: 3 AC 400-480 V output: 24 V DC/8 A
Input
Input3-phase AC
Rated voltage value Vin rated400 ... 480 V
Voltage range AC340 ... 550 V
Note320 ... 340 V for max. 1 min
Wide-range inputYes
Overvoltage resistanceImplemented internally with varistors
Mains buffering at Iout rated, min.15 ms; at Vin = 400 V
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range45 ... 66 Hz
Input current
at rated input voltage 400 V0.5 A
Switch-on current limiting (+25 °C), max.40 A
I²t, max.3.5 A²·s
Built-in incoming fuseT 4 A
Protection in the mains power input (IEC 898)Required: Circuit breaker 3RV2011-1DA10 or 3RV2711-1DD10 (UL 489)
Output
OutputControlled, isolated DC voltage
Rated voltage Vout DC24 V
Total tolerance, static ±3 %
Static mains compensation, approx.0.5 %
Static load balancing, approx.0.5 %
Residual ripple peak-peak, max.200 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)250 mV
Product function Output voltage adjustableNo
Output voltage setting-
Status displayGreen LED for 24 V OK
Signalingmax. 30 V, 10 mA; Power-Good (High-Pegel 1L+ for Vout in range 21.3 ... 29 V); Overtemperature warning at least 30 s before switch-off (high level 1L+ when the max. internal temperature is exceeded)
On/off behaviorOvershoot of Vout < 2 %
Startup delay, max.1.5 s
Voltage rise, typ.40 ms
Rated current value Iout rated8 A
Current range0 ... 8 A
Supplied active power typical192 W
Short-term overload current
on short-circuiting during the start-up typical50 A
at short-circuit during operation typical50 A
Duration of overloading capability for excess current
on short-circuiting during the start-up100 ms
at short-circuit during operation100 ms
Parallel switching for enhanced performanceNo
Efficiency
Efficiency at Vout rated, Iout rated, approx.88 %
Power loss at Vout rated, Iout rated, approx.25 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.0.5 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.1 %
Setting time maximum2 ms
Protection and monitoring
Output overvoltage protection< 33 V
Current limitation, typ.9.4 A
Property of the output Short-circuit proofYes
Short-circuit protectionElectronic shutdown, automatic restart
Enduring short circuit current RMS value
maximum10 A
Overload/short-circuit indicator-
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection classClass I
Leakage current
maximum3.5 mA
typical0.4 mA
CE markYes
UL/cUL (CSA) approvalUL-Listed (UL 508) according to NFPA compatibility (National Fire Protection Association), see operating instructions
Explosion protection-
FM approval-
CB approvalYes
Marine approval-
Degree of protection (EN 60529)IP67, enclosure type 5 indoor
EMC
Emitted interferenceEN 55022 Class A
Supply harmonics limitation-
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation-25 ... +55 °C
— Notewith natural convection
during transport-40 ... +70 °C
during storage-40 ... +70 °C
Humidity class according to EN 60721Climate class 3K3, no condensation
Mechanics
Connection technologyscrew-type terminals
Connections
Supply inputL1, L2, L3, PE: Plug connector HAN Q4/2 (counterpart see "Electrical accessories")
OutputL+, M: 1 x 2 mm² each (2-pole cable for +/- with open, labeled ends, 2 x 2 mm²)
AuxiliaryAlarm signals: M12 plug-in connector 5-pin
Width of the enclosure310 mm
Height of the enclosure135 mm
Depth of the enclosure90 mm
Weight, approx.2.8 kg
Product feature of the enclosure housing for side-by-side mountingNo
InstallationCan be mounted onto ET200pro mounting rail
Electrical accessoriesPower connector (3RK1911-2BE50 (2.5mm²))
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

External links