6AG1322-1FH00-7AA0
SIPLUS S7-300 SM322 16DO

From SIEMENS

SIPLUS S7-300 SM 322 16DO -40...+70°C with conformal coating based on 6ES7322-1FH00-0AA0 . Digital output Isolated 16 DO, 120/230 V AC, 1 A, 1x 20-pole
Supply voltage
Load voltage L1
Rated value (AC)230 V; 120/230 V AC
permissible range, lower limit (AC)79 V
permissible range, upper limit (AC)264 V
Input current
from load voltage L1 (without load), max.2 mA
from backplane bus 5 V DC, max.200 mA
Power loss
Power loss, typ.8.6 W
Digital outputs
Number of digital outputs16
Switching capacity of the outputs
on lamp load, max.50 W
Output current
for signal "1" rated value1 A
for signal "1" minimum load current10 mA
for signal "1" permissible surge current, max.20 A; with 2 half waves
for signal "0" residual current, max.2 mA
Switching frequency
with resistive load, max.10 Hz
with inductive load, max.0.5 Hz
on lamp load, max.1 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.4 A
— up to 60 °C, max.2 A
— up to 70 °C, max.1 A
vertical installation
— up to 40 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionYes; Fuse blown or load voltage missing
Alarms
Diagnostic alarmNo
Diagnostic messages
Wire-breakNo
Short-circuitNo
Fuse blownYes
missing load voltageNo
Diagnostics indication LED
Rated load voltage PWR (green)No
Fuse OK FSG (green)Yes; Red LED for fuse
Group error SF (red)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital outputs
between the channels, in groups of8
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with4 000 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50121-4No
EN 50155No
Ambient conditions
Ambient temperature during operation
min.-40 °C; = Tmin
max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.275 g
last modified:03/13/2019