6AG1211-1AE31-4XB0
SIPLUS S7-1200 CPU1211 DC/DC/DC

From SIEMENS

SIPLUS S7-1200 CPU 1211C DC/DC/DC for medial exposure with conformal coating based on 6ES7211-1AE31-0XB0 . compact CPU, DC/DC/DC, onboard I/O: 6 DI 24 V DC 4 DO 24 V DC 2 AI 0-10 V DC, Power supply: 20.4-28.8V Program/data memory 30 KB
General information
Product type designationCPU 1211C DC/DC/DC
Engineering with
Programming packageSTEP 7 V11 SP2 or higher
Supply voltage
Rated value (DC)
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption (rated value)300 mA; Typical
Current consumption, max.0.9 A; 24 V DC
Inrush current, max.12 A; at 28.8 V DC
Output current
for backplane bus (5 V DC), max.750 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
24 VPermissible range: 20.4V to 28.8V
Power loss
Power loss, typ.8 W
Memory
Work memory
integrated30 kbyte
expandableNo
Load memory
integrated1 Mbyte
Backup
presentmaintenance-free
without batteryYes
CPU processing times
for bit operations, typ.0.085 µs; / instruction
for word operations, typ.1.7 µs; / instruction
for floating point arithmetic, typ.2.5 µs; / instruction
CPU-blocks
Number of blocks (total)DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
Number, max.Limited only by RAM for code
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.10 kbyte
Flag
Number, max.4 kbyte; Size of bit memory address area
Address area
I/O address area
Inputs1 024 byte
Outputs1 024 byte
Process image
Inputs, adjustable1 kbyte
Outputs, adjustable1 kbyte
Hardware configuration
Number of modules per system, max.3 communication modules, 1 signal board
Time of day
Clock
Hardware clock (real-time)Yes
Backup time480 h; Typical
Deviation per day, max.±60 s/month at 25 °C
Digital inputs
Number of digital inputs6; Integrated
of which inputs usable for technological functions3; HSC (High Speed Counting)
Source/sink inputYes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.6
Input voltage
Rated value (DC)24 V
for signal "0"5 V DC at 1 mA
for signal "1"15 V DC at 2.5 mA
Input current
for signal "1", typ.1 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
— at "0" to "1", min.0.2 ms
— at "0" to "1", max.12.8 ms
for interrupt inputs
— parameterizableYes
for technological functions
— parameterizableSingle phase : 3 @ 100 kHz, differential: 3 @ 80 kHz
Cable length
shielded, max.500 m; 50 m for technological functions
unshielded, max.300 m; for technological functions: No
Digital outputs
Number of digital outputs4
of which high-speed outputs4; 100 kHz Pulse Train Output
Short-circuit protectionNo; to be provided externally
Limitation of inductive shutdown voltage toL+ (-48 V)
Switching capacity of the outputs
with resistive load, max.0.5 A
on lamp load, max.5 W
Output voltage
for signal "0", max.0.1 V; with 10 kOhm load
for signal "1", min.20 V
Output current
for signal "1" rated value0.5 A
for signal "0" residual current, max.0.1 mA
Output delay with resistive load
"0" to "1", max.1 µs
"1" to "0", max.5 µs
Switching frequency
of the pulse outputs, with resistive load, max.100 kHz
Relay outputs
Number of relay outputs0
Cable length
shielded, max.500 m
unshielded, max.150 m
Analog inputs
Number of analog inputs2
Input ranges
VoltageYes
Input ranges (rated values), voltages
0 to +10 VYes
— Input resistance (0 to 10 V)≥100k ohms
Cable length
shielded, max.100 m; twisted and shielded
Analog outputs
Number of analog outputs0
Cable length
shielded, max.100 m; shielded, twisted pair
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.10 bit
Integration time, parameterizableYes
Conversion time (per channel)625 µs
Encoder
Connectable encoders
2-wire sensorYes
1. Interface
Interface typePROFINET
PhysicsEthernet
IsolatedYes
automatic detection of transmission rateYes
AutonegotiationYes
AutocrossingYes
Protocols
PROFINET IO ControllerYes
Protocols
Supports protocol for PROFINET IOYes
PROFIBUSYes
AS-InterfaceYes
Protocols (Ethernet)
TCP/IPYes
Open IE communication
TCP/IPYes
ISO-on-TCP (RFC1006)Yes
UDPYes
Web server
supportedYes
User-defined websitesYes
Further protocols
MODBUSYes
Communication functions
S7 communication
supportedYes
as serverYes
as clientYes
Test commissioning functions
Status/control
Status/control variableYes
VariablesInputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
ForcingYes
Diagnostic buffer
presentYes
Integrated Functions
Number of counters3
Counting frequency (counter) max.100 kHz
Frequency measurementYes
controlled positioningYes
PID controllerYes
Number of alarm inputs4
Number of pulse outputs4
Limit frequency (pulse)100 kHz
Potential separation
Potential separation digital inputs
Potential separation digital inputs500V AC for 1 minute
between the channels, in groups of1
Potential separation digital outputs
Potential separation digital outputsYes
between the channelsNo
between the channels, in groups of1
Permissible potential difference
between different circuits500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2Yes
— Test voltage at air discharge8 kV
— Test voltage at contact discharge6 kV
Interference immunity to cable-borne interference
Interference immunity on supply lines acc. to IEC 61000-4-4Yes
Interference immunity on signal cables acc. to IEC 61000-4-4Yes
Interference immunity against voltage surge
Interference immunity on supply lines acc. to IEC 61000-4-5Yes
Interference immunity against conducted variable disturbance induced by high-frequency fields
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6Yes
Emission of radio interference acc. to EN 55 011
Limit class A, for use in industrial areasYes; Group 1
Limit class B, for use in residential areasYes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
IP degree of protectionIP20
Ambient conditions
Free fall
Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation
min.-20 °C; = Tmin; Startup @ 0 °C
max.60 °C; = Tmax
horizontal installation, min.-20 °C; = Tmin (incl. condensation/frost); start-up @ 0 °C
horizontal installation, max.60 °C; = Tmax
vertical installation, min.-20 °C; = Tmin; Startup @ 0 °C
vertical installation, max.50 °C; = Tmax
At cold restart, min.0 °C
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Vibrations
Vibration resistance during operation acc. to IEC 60068-2-62 g (m/s²) wall mounting, 1 g (m/s²) DIN rail
Operation, tested according to IEC 60068-2-6Yes
Shock testing
tested according to IEC 60068-2-27Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Resistance
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Configuration
Programming
Programming language
— LADYes
— FBDYes
— SCLYes
Cycle time monitoring
adjustableYes
Dimensions
Width90 mm
Height100 mm
Depth75 mm
Weights
Weight, approx.370 g
last modified:02/22/2020