5SU1354-1KK20
RCBO elm

From SIEMENS

RCBO, 10 kA, 1P+N, Type AC, 30 mA, C-Char, In: 20 A, Un AC: 230 V
Model
Product brand nameSENTRON
Product designationRCBO
Design of the productInstantaneous
General technical data
Number of poles2
Number of poles / Note1P+N
Number of poles / with protection1
Tripping characteristic classC
circuit-breaker / Design5SU1
Mechanical service life (switching cycles) / typical10 000
Overvoltage categoryIII
Voltage
Surge current resistance / at (8/20) µs1 kA
Supply voltage
Supply voltage
for testing equipment / minimum195 V
Supply voltage frequency / rated value50 Hz
Protection class
Protection class IPIP20, if the distribution board is installed, with connected conductors
Energy limiting class3
Switching capacity
Switching capacity current
acc. to EN 60898 / rated value10 kA
acc. to IEC 60947-2 / rated value20 kA
Rated residual switching capacity (IΔm) / according to IEC 61009-110 kA
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole3.3 W
Electricity
Tripping residual current / rated value30 mA
Tripping residual / rated value / derated current
at 30 Cel20 A
at 40 Cel18.8 A
at 45 Cel18.2 A
at 50 Cel17.4 A
at 55 Cel16.2 A
at 60 Cel16.2 A
at 65 Cel15.4 A
at 70 Cel14.6 A
Type of fault currentAC
Current / at AC / rated value20 A
Product details
Product feature / Touch protectionYes
Product feature
halogen-freeYes
silicon-freeYes
Product function
Product function / neutral conductor switchingYes
Number
Number of test cycles / for environmental testing / acc. to IEC 60068-2-3028
Connections
Connectable conductor cross-section / stranded
minimum0.75 mm²
maximum35 mm²
Connectable conductor cross-section
solid
— minimum0.75 mm²
— maximum35 mm²
finely stranded / with core end processing
— minimum0.75 mm²
— maximum25 mm²
Tightening torque / with screw-type terminals
minimum2.5 N·m
maximum3 N·m
Position / of power supply cordEither top or bottom
Mechanical Design
Height90 mm
Width36 mm
Depth77 mm
Mounting positionany
Installation depth70 mm
Number of width units2
Net weight278 g
Environmental conditions
Degree of pollution2
Influence of the surrounding temperatureMax. 95% humidity
Ambient temperature
minimum-25 °C
maximum55 °C
during storage / minimum-40 °C
during storage / maximum75 °C

External links