5SM3346-0LA
RCCB

From SIEMENS

Residual current operated circuit breaker, 4-pole, type AC, In: 63 A, 30 mA, Un AC: 400 V, with thermal overload protection
Model
Product brand nameSENTRON
Product designationRCCB
Design of the productInstantaneous
Product variationsWith thermal overload protection
General technical data
Number of poles4
Size of installation devices / acc. to DIN 438801
Protection against electrical shockFinger and back-of-hand safe
Short-circuit current rating10 kA
circuit-breaker / Design5SM3
Mechanical service life (switching cycles) / typical10 000
Switching function / short-term delayedNo
Overvoltage categoryIII
Supply voltage
Supply voltage
at AC / rated value400 V
for testing equipment / minimum195 V
Supply voltage frequency
rated value50 Hz
Protection class
Protection class IPIP20, if the distribution board is installed, with connected conductors
Switching capacity
Switching capacity current / according to IEC 61008-1 / rated value0.8 kA
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole4.9 W
Electricity
Tripping residual current / rated value30 mA
Type of fault currentAC
Current / at AC / rated value63 A
Operating frequency50Hz
Product details
Product feature / silicon-freeYes
Product extension / can be installed / supplementary devicesYes
Number
Number of test cycles / for environmental testing / acc. to IEC 60068-2-3028
Connections
Connectable conductor cross-section / stranded
minimum1.5 mm²
maximum25 mm²
Connectable conductor cross-section / solid
minimum1.5 mm²
maximum25 mm²
Tightening torque / with screw-type terminals
minimum2.5 N·m
maximum3 N·m
Position / of power supply cordtop or bottom
Mechanical Design
Mounting positionany
Installation depth70 mm
Number of width units4
Mounting typeDIN rail (REG)
Net weight505 g
Environmental conditions
Ambient temperature
minimum-5 °C
maximum45 °C
during storage / minimum permissible-40 °C
during storage / maximum permissible75 °C

External links