4BU6096-0EB58-6YA0 TR PN(KVA):200 UPRI(V):440+/-7,5%+/-15%
From SIEMENS
CONVERTER TRANSFORMER; PHASES:3; PN(KVA):200; UPRI(V):440+/-7,5%+/-15%; USEC(V):300; ISEC(A):385; UK(%):4; F(HZ):60...60; VECTOR GR./SHIELD WNG.:DY5 /0; TA/ISOKL:40 /H; IP00; TYPE OF TERMINALS:FLAT-TYPE TERMINAL; INSTALLATION:SCREW; VDE 0532 | |||
General technical data: | |||
Product designation | converter transformer | ||
Product brand name | SIDAC | ||
Operating apparent output rated value | V·A | 200 000 | |
Efficiency | 0.97 | ||
Connection method for transformers | Dy5 | ||
Certificate of suitability | CE | ||
Product function | |||
Temperature monitoring | No | ||
Insulation monitoring | No | ||
Short-circuit and overload proof | No | ||
Number of shielding windings | 0 | ||
Relative short-circuit voltage | % | 4 | |
Inputs: | |||
Phase number of the inputs | 3 | ||
Input voltage | |||
_1 rated value | V | 506 | |
_2 rated value | V | 473 | |
_3 rated value | V | 440 | |
_4 rated value | V | 407 | |
_5 rated value | V | 374 | |
Electrical input frequency | |||
minimum | Hz | 60 | |
maximum | Hz | 60 | |
Outputs: | |||
Phase number of the outputs | 3 | ||
Output voltage | |||
_1 rated value | V | 300 | |
Electrical output frequency | |||
maximum | Hz | 60 | |
minimum | Hz | 60 | |
Ambient conditions: | |||
Thermal class acc. to IEC 60085 | H | ||
Ambient temperature rated value | °C | 40 | |
Protection class IP | IP00 | ||
Mechanical data: | |||
Type of electrical connection | |||
at output for main current circuit | flat connector | ||
at input for main current circuit | flat connector | ||
Mounting type | screws | ||
Construction form of the iron core | 3UIS 395/195 | ||
Width | m | 0.855 | |
Height | m | 0.686 | |
Depth | m | 0.23 |