3RT2317-2AP00
4NO CONTACTOR, AC1: 22A, 230V 50/60HZ

From SIEMENS

Contactor, 4 NO, AC-1: 22 A 230 V AC, 50 / 60 Hz, 4-pole, 4 NO, Size S00, Spring-type terminal
Product brand nameSIRIUS
Product designationContactor
Product type designation3RT23
General technical data
Size of contactorS00
Product extension
function module for communicationNo
Auxiliary switchYes
Surge voltage resistance
of main circuit rated value6 kV
of auxiliary circuit rated value6 kV
Protection class IP
on the frontIP20
of the terminalIP20
Shock resistance at rectangular impulse
at AC7,3g / 5 ms, 4,7g / 10 ms
Shock resistance with sine pulse
at AC11,4g / 5 ms, 7,3g / 10 ms
Reference code acc. to DIN EN 81346-2Q
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Main circuit
Number of poles for main current circuit4
Number of NO contacts for main contacts4
Operating current
at AC-1
— up to 690 V at ambient temperature 40 °C rated value22 A
— up to 690 V at ambient temperature 60 °C rated value20 A
at AC-3
— at 400 V rated value12 A
at AC-4 at 400 V rated value8.5 A
Connectable conductor cross-section in main circuit at AC-1
at 60 °C minimum permissible2.5 mm²
at 40 °C minimum permissible4 mm²
Operating power
at AC-3
— at 400 V rated value5.5 kW
at AC-4 at 400 V rated value4 kW
No-load switching frequency
at AC10 000 1/h
Operating frequency
at AC-1 maximum1 000 1/h
Control circuit/ Control
Type of voltage of the control supply voltageAC
Control supply voltage at AC
at 50 Hz rated value230 V
at 60 Hz rated value230 V
Operating range factor control supply voltage rated value of magnet coil at AC
at 50 Hz0.8 ... 1.1
at 60 Hz0.85 ... 1.1
Apparent pick-up power of magnet coil at AC
at 50 Hz37 V·A
at 60 Hz33 V·A
Inductive power factor with closing power of the coil
at 50 Hz0.8
at 60 Hz0.75
Apparent holding power of magnet coil at AC
at 50 Hz5.7 V·A
at 60 Hz4.4 V·A
Inductive power factor with the holding power of the coil
at 50 Hz0.25
at 60 Hz0.25
Closing delay
at AC8 ... 33 ms
Opening delay
at AC4 ... 15 ms
Arcing time10 ... 15 ms
Control version of the switch operating mechanismStandard A1 - A2
Short-circuit protection
Design of the fuse link
for short-circuit protection of the main circuit
— with type of coordination 1 requiredgG: 35 A (690 V, 100 kA)
— with type of assignment 2 requiredgG: 20 A (690 V, 100 kA)
for short-circuit protection of the auxiliary switch requiredgG: 10 A (690 V, 1 kA)
Installation/ mounting/ dimensions
Mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
Mounting typescrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Side-by-side mountingYes
Height70 mm
Width45 mm
Depth73 mm
Required spacing
with side-by-side mounting
— forwards10 mm
— upwards10 mm
— downwards10 mm
— at the side0 mm
for grounded parts
— forwards10 mm
— upwards10 mm
— at the side6 mm
— downwards10 mm
for live parts
— forwards10 mm
— upwards10 mm
— downwards10 mm
— at the side6 mm
Connections/Terminals
Type of electrical connection
for main current circuitspring-loaded terminals
for auxiliary and control current circuitspring-loaded terminals
Type of connectable conductor cross-sections
for main contacts
— solid2x (0.5 ... 4 mm²)
— single or multi-stranded2x (0,5 ... 4 mm²)
— finely stranded with core end processing2x (0.5 ... 2.5 mm²)
— finely stranded without core end processing2x (0.5 ... 2.5 mm²)
at AWG conductors for main contacts2x (20 ... 12)
Connectable conductor cross-section for main contacts
solid0.5 ... 4 mm²
single or multi-stranded0.5 ... 4 mm²
stranded0.5 ... 4 mm²
finely stranded with core end processing0.5 ... 2.5 mm²
finely stranded without core end processing0.5 ... 2.5 mm²
Connectable conductor cross-section for auxiliary contacts
single or multi-stranded0.5 ... 4 mm²
finely stranded with core end processing0.5 ... 2.5 mm²
finely stranded without core end processing0.5 ... 2.5 mm²
Type of connectable conductor cross-sections
for auxiliary contacts
— single or multi-stranded2x (0,5 ... 4 mm²)
— finely stranded with core end processing2x (0.5 ... 2.5 mm²)
— finely stranded without core end processing2x (0.5 ... 2.5 mm²)
at AWG conductors for auxiliary contacts2x (20 ... 12)
AWG number as coded connectable conductor cross section
for main contacts20 ... 12
for auxiliary contacts20 ... 12
Safety related data
Product function
Mirror contact acc. to IEC 60947-4-1Yes; with 3RH29
T1 value for proof test interval or service life acc. to IEC 6150820 y
Protection against electrical shockfinger-safe