| Thermistor motor protection relay Standard evaluation unit 22.5 mm enclosure screw terminal 2 change-over contacts US = 24 V-240 V AC/DC Manual/Auto/Remote reset with ATEX approval 2 LEDs (READY/TRIPPED) galvanic isolation Test/reset button Wire break monitoring Short circuit monitoring non-volatile |
Product brand name | SIRIUS |
Product category | SIRIUS 3RN2 thermistor motor protection |
Product designation | Thermistor motor protection relay |
Design of the product | Standard evaluation unit with ATEX approval, open-circuit and short-circuit detection in the sensor circuit, non-volatile |
Product type designation | 3RN2 |
General technical data |
Display version LED | Yes |
Power loss [W] for rated value of the current | |
at AC in hot operating state | 1.7 W |
at DC in hot operating state | 1.7 W |
Insulation voltage | |
for overvoltage category III according to IEC 60664 | |
— with degree of pollution 3 rated value | 300 V |
Degree of pollution | 3 |
Surge voltage resistance rated value | 4 kV |
Protection class IP | IP20 |
Shock resistance | |
acc. to IEC 60068-2-27 | 11g / 15 ms |
Mechanical service life (switching cycles) | |
typical | 10 000 000 |
Electrical endurance (switching cycles) | |
at AC-15 at 230 V typical | 100 000 |
Thermal current of the switching element with contacts maximum | 5 A |
Certificate of suitability relating to ATEX | PTB 15 ATEX 3011 |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | K |
Reference code acc. to DIN EN 81346-2 | K |
Reference code acc. to DIN EN 61346-2 | K |
Control circuit/ Control |
Type of voltage of the control supply voltage | AC/DC |
Control supply voltage at AC | |
at 50 Hz rated value | 24 ... 240 V |
at 60 Hz rated value | 24 ... 240 V |
Control supply voltage at DC | |
rated value | 24 ... 240 V |
Operating range factor control supply voltage rated value at DC | |
initial value | 0.85 |
Full-scale value | 1.1 |
Operating range factor control supply voltage rated value at AC at 50 Hz | |
initial value | 0.85 |
Full-scale value | 1.1 |
Operating range factor control supply voltage rated value at AC at 60 Hz | |
initial value | 0.85 |
Full-scale value | 1.1 |
Inrush current peak | |
at 24 V | 0.7 A |
at 240 V | 12 A |
Duration of inrush current peak | |
at 24 V | 0.25 ms |
at 240 V | 0.2 ms |
Measuring circuit |
Buffering time in the event of power failure minimum | 40 ms |
Precision |
Relative metering precision | 2 % |
Auxiliary circuit |
Material of switching contacts | AgSnO2 |
Number of NC contacts for auxiliary contacts | 0 |
Number of NO contacts for auxiliary contacts | 0 |
Number of CO contacts | |
for auxiliary contacts | 2 |
Operating current of auxiliary contacts at DC-13 | |
at 24 V | 1 A |
at 125 V | 0.2 A |
at 250 V | 0.1 A |
Main circuit |
Operating frequency rated value | 50 ... 60 Hz |
Outputs |
Ampacity of the output relay at AC-15 | |
at 250 V at 50/60 Hz | 3 A |
Ampacity of the output relay at DC-13 | |
at 24 V | 1 A |
at 125 V | 0.2 A |
Continuous current of the DIAZED fuse link of the output relay | 6 A |
Electromagnetic compatibility |
Conducted interference | |
due to burst acc. to IEC 61000-4-4 | 2 kV (power ports) / 1 kV (signal ports) |
due to conductor-earth surge acc. to IEC 61000-4-5 | 2 kV (line to ground) |
due to conductor-conductor surge acc. to IEC 61000-4-5 | 1 kV (line to line) |
Electrostatic discharge acc. to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
Galvanic isolation |
Design of the electrical isolation | galvanic isolation |
Galvanic isolation | |
between entrance and outlet | Yes |
between the outputs | Yes |
between the voltage supply and other circuits | Yes |
Safety related data |
Safety Integrity Level (SIL) acc. to IEC 61508 | 1 |
Performance level (PL) acc. to EN ISO 13849-1 | c |
Category acc. to EN ISO 13849-1 | 1 |
Safe failure fraction (SFF) | 74 % |
Average diagnostic coverage level (DCavg) | 18 % |
Failure rate [FIT] | |
at rate of recognizable hazardous failures (λdd) | 0.000000068 1/h |
at rate of non-recognizable hazardous failures (λdu) | 0.00000031 1/h |
PFHD with high demand rate acc. to EN 62061 | 0.00000038 1/h |
PFDavg with low demand rate acc. to IEC 61508 | 0.0041 |
MTBF | 97 y |
MTTFd | 303 y |
Hardware fault tolerance acc. to IEC 61508 | 0 |
T1 value for proof test interval or service life acc. to IEC 61508 | 3 y |
Connections/Terminals |
Product function | |
removable terminal for auxiliary and control circuit | Yes |
Type of electrical connection | screw-type terminals |
Type of connectable conductor cross-sections | |
solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
finely stranded with core end processing | 1x (0.5 ... 4 mm²), 2x (0.5 ... 1.5 mm²) |
at AWG conductors solid | 1x (20 ... 12), 2x (20 ... 14) |
Connectable conductor cross-section | |
solid | 0.5 ... 4 mm² |
finely stranded with core end processing | 0.5 ... 4 mm² |
AWG number as coded connectable conductor cross section | |
solid | 20 ... 12 |
stranded | 20 ... 12 |
Tightening torque | |
with screw-type terminals | 0.6 ... 0.8 N·m |
Installation/ mounting/ dimensions |
Mounting position | any |
Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail |
Height | 100 mm |
Width | 22.5 mm |
Depth | 90 mm |
Required spacing | |
with side-by-side mounting | |
— forwards | 0 mm |
— Backwards | 0 mm |
— upwards | 0 mm |
— downwards | 0 mm |
— at the side | 0 mm |
for grounded parts | |
— forwards | 0 mm |
— Backwards | 0 mm |
— upwards | 0 mm |
— at the side | 0 mm |
— downwards | 0 mm |
for live parts | |
— forwards | 0 mm |
— Backwards | 0 mm |
— upwards | 0 mm |
— downwards | 0 mm |
— at the side | 0 mm |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Ambient temperature | |
during operation | -25 ... +60 °C |
during storage | -40 ... +85 °C |
during transport | -40 ... +85 °C |
Relative humidity | |
during operation | 70 % |
Explosion protection category for dust | [Ex t] [Ex p] |