3RN2012-1BW30
THERMISTOR MOTOR PROT. 2CO REMOTE RESET

From SIEMENS

Thermistor motor protection relay Standard evaluation unit 22.5 mm enclosure screw terminal 2 change-over contacts US = 24 V-240 V AC/DC Manual/Auto/Remote reset with ATEX approval 2 LEDs (READY/TRIPPED) galvanic isolation Test/reset button Wire break monitoring Short circuit monitoring non-volatile
Product brand nameSIRIUS
Product categorySIRIUS 3RN2 thermistor motor protection
Product designationThermistor motor protection relay
Design of the productStandard evaluation unit with ATEX approval, open-circuit and short-circuit detection in the sensor circuit, non-volatile
Product type designation3RN2
General technical data
Display version LEDYes
Power loss [W] for rated value of the current
at AC in hot operating state1.7 W
at DC in hot operating state1.7 W
Insulation voltage
for overvoltage category III according to IEC 60664
— with degree of pollution 3 rated value300 V
Degree of pollution3
Surge voltage resistance rated value4 kV
Protection class IPIP20
Shock resistance
acc. to IEC 60068-2-2711g / 15 ms
Mechanical service life (switching cycles)
typical10 000 000
Electrical endurance (switching cycles)
at AC-15 at 230 V typical100 000
Thermal current of the switching element with contacts maximum5 A
Certificate of suitability relating to ATEXPTB 15 ATEX 3011
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750K
Reference code acc. to DIN EN 81346-2K
Reference code acc. to DIN EN 61346-2K
Control circuit/ Control
Type of voltage of the control supply voltageAC/DC
Control supply voltage at AC
at 50 Hz rated value24 ... 240 V
at 60 Hz rated value24 ... 240 V
Control supply voltage at DC
rated value24 ... 240 V
Operating range factor control supply voltage rated value at DC
initial value0.85
Full-scale value1.1
Operating range factor control supply voltage rated value at AC at 50 Hz
initial value0.85
Full-scale value1.1
Operating range factor control supply voltage rated value at AC at 60 Hz
initial value0.85
Full-scale value1.1
Inrush current peak
at 24 V0.7 A
at 240 V12 A
Duration of inrush current peak
at 24 V0.25 ms
at 240 V0.2 ms
Measuring circuit
Buffering time in the event of power failure minimum40 ms
Precision
Relative metering precision2 %
Auxiliary circuit
Material of switching contactsAgSnO2
Number of NC contacts for auxiliary contacts0
Number of NO contacts for auxiliary contacts0
Number of CO contacts
for auxiliary contacts2
Operating current of auxiliary contacts at DC-13
at 24 V1 A
at 125 V0.2 A
at 250 V0.1 A
Main circuit
Operating frequency rated value50 ... 60 Hz
Outputs
Ampacity of the output relay at AC-15
at 250 V at 50/60 Hz3 A
Ampacity of the output relay at DC-13
at 24 V1 A
at 125 V0.2 A
Continuous current of the DIAZED fuse link of the output relay6 A
Electromagnetic compatibility
Conducted interference
due to burst acc. to IEC 61000-4-42 kV (power ports) / 1 kV (signal ports)
due to conductor-earth surge acc. to IEC 61000-4-52 kV (line to ground)
due to conductor-conductor surge acc. to IEC 61000-4-51 kV (line to line)
Electrostatic discharge acc. to IEC 61000-4-26 kV contact discharge / 8 kV air discharge
Galvanic isolation
Design of the electrical isolationgalvanic isolation
Galvanic isolation
between entrance and outletYes
between the outputsYes
between the voltage supply and other circuitsYes
Safety related data
Safety Integrity Level (SIL) acc. to IEC 615081
Performance level (PL) acc. to EN ISO 13849-1c
Category acc. to EN ISO 13849-11
Safe failure fraction (SFF)74 %
Average diagnostic coverage level (DCavg)18 %
Failure rate [FIT]
at rate of recognizable hazardous failures (λdd)0.000000068 1/h
at rate of non-recognizable hazardous failures (λdu)0.00000031 1/h
PFHD with high demand rate acc. to EN 620610.00000038 1/h
PFDavg with low demand rate acc. to IEC 615080.0041
MTBF97 y
MTTFd303 y
Hardware fault tolerance acc. to IEC 615080
T1 value for proof test interval or service life acc. to IEC 615083 y
Connections/Terminals
Product function
removable terminal for auxiliary and control circuitYes
Type of electrical connectionscrew-type terminals
Type of connectable conductor cross-sections
solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
finely stranded with core end processing1x (0.5 ... 4 mm²), 2x (0.5 ... 1.5 mm²)
at AWG conductors solid1x (20 ... 12), 2x (20 ... 14)
Connectable conductor cross-section
solid0.5 ... 4 mm²
finely stranded with core end processing0.5 ... 4 mm²
AWG number as coded connectable conductor cross section
solid20 ... 12
stranded20 ... 12
Tightening torque
with screw-type terminals0.6 ... 0.8 N·m
Installation/ mounting/ dimensions
Mounting positionany
Mounting typescrew and snap-on mounting onto 35 mm standard mounting rail
Height100 mm
Width22.5 mm
Depth90 mm
Required spacing
with side-by-side mounting
— forwards0 mm
— Backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
for grounded parts
— forwards0 mm
— Backwards0 mm
— upwards0 mm
— at the side0 mm
— downwards0 mm
for live parts
— forwards0 mm
— Backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Ambient temperature
during operation-25 ... +60 °C
during storage-40 ... +85 °C
during transport-40 ... +85 °C
Relative humidity
during operation70 %
Explosion protection category for dust[Ex t] [Ex p]

External links