3RK2400-1BQ20-0AA3
AS-INTERFACE COMP. MODULE K45,

From SIEMENS

AS-i compact module K45 digital A/B slave, 2 DI/2 DQ, IP67 2 x input, maximum 200 mA 2 x output, 2 A 24 V DC maximal 3 A for all outputs 4 x M12 socket Mounting plate 3RK1901-2EA00 or 3RK1901-2DA00 is to be ordered separately
General technical data
Design of the productdigital I/O modules for operation in the field, IP67 - K45
Type2 outputs / 2 inputs
Design of the slave typeA/B slave
I/O configurationB
ID/ID2 codeA/0
Number I/O sockets4
Type of electrical connection of the inputs and outputsM12 screw-type terminals
AS interface total current input max270 mA
operating voltage according to AS-Interface spezification26.5 ... 31.6 V
Ground terminalUsing PIN5 on the M12 sockets. Outgoing via flat tab sleeve (2.8 x 0.8 mm form A)
Addressingfront addressing socket
AS interface Connection Polarity reversal protectionbuilt-in
Delivery notethe modules are delivered without mounting plate
Note 1An external additional supply (AUX POWER) of 20 to 30 V DC is required for the supply of the output circuits. The additional supply must comply with VDE 0106 (PELV), protection class III.
Sensor supply
Type of voltage supply for power supplyusing AS-Interface
Input voltage16.5 ... 30 V
Property of the sensor supply Short-circuit and overload resistantYes
Ampacity of the sensor supply for all inputs
at ambient temperature 40 °C200 mA
Inputs
Number of digital inputs2
Type of connection2- and 3-wire technology
Input circuitPNP transistor
Type of voltage of the input voltagesDC
Inputs switching level High min10 V
Input current at digital input
for signal <1> minimum6 mA
with signal <0> maximum1.5 mA
Inputs sensor supply using AS-Interfaceshort-circuit and overload resistant
Inputs socket assignment
PIN 1sensor supply L+
PIN 2data input
PIN 3sensor supply L-
PIN 4data input
PIN 5ground terminal
Design of the pin assignment of the inputsstandard assignement
Outputs
Number of digital outputs2
Type of voltage of output voltagesDC
Outputs external power supply 24 V DCusing black AS-Interface flat cable
Ampacity of the semiconductor output at DC-13 at 24 V1.5 A
Outputs aggregate current
max3 A
Type of switching outputPNP transistor
Design of the pin assignment of the outputsstandard assignement
Outputs socket assignment3 = "-", 4 = output, 5 = ground terminal
Property of the output Short-circuit proofYes
Outputs
short-ciruit protectionbuilt-in
induction protectionbuilt-in
watchdogbuilt-in
Status display
display of I/Osyellow LED
display of Uauxgreen LED
display of AS-Interface/diagnosticsgreen/red dual LED
Assignment of data bits
socketPIN 4/2 = IN3 (D2)
socket 2PIN 4/2 = IN4 (D3)
socket 3PIN 4 = OUT1 (D0)
socket 4PIN 4 = OUT2 (D1)
Ambient conditions
Ambient temperature
during operation-25 ... +85 °C
during storage-40 ... +85 °C
Protection class IPIP67
Mechanical data
Width45 mm
Height80 mm
Depth30 mm
Mounting typestandard rail mounting/wall mounting using mounting plate for K45 compact module

External links