3RK1325-6KS41-2AA0
MOTOR STARTER M200D AS-I STANDARD

From SIEMENS

SIRIUS motor starter M200D AS-i Communication: AS-Interface DOL starter Standard Mechanical switching AC-3, 0.75KW / 400 V 0.15 A...2.00 A Electronic overload protection Thermistor: THERMOCLICK / PTC without brake contact 4 DI / 1 DO AS-i Han Q4/2 - Han Q8/0 with manual on-site operation and key-operated switch
Product brand nameSIRIUS
Product designationMotor starters
Design of the productdirect starter
Product type designationM200D
Product function
on-site operationYes
Control circuit interface to parallel wiringNo
Power loss [W] typical30 W
Insulation voltage rated value500 V
Degree of pollution3
Surge voltage resistance rated value6 000 V
maximum permissible voltage for safe isolation
between main and auxiliary circuit400 V
between control and auxiliary circuit24 V
Protection class IPIP65
Shock resistance12g / 11 ms
Mechanical service life (switching cycles) of the main contacts typical10 000 000
Type of assignment2
Certificate of suitabilityCE
Reference code acc. to DIN EN 61346-2Q
Product function
direct startYes
reverse startingNo
Product component Motor brake outputNo
Product feature
brake control with 230 V ACNo
brake control with 400 V ACNo
brake control with 24 V DCNo
brake control with 180 V DCNo
brake control with 500 V DCNo
Product extension braking module for brake controlNo
Product function Short circuit protectionYes
Design of short-circuit protectioncircuit-breakers
Trip classCLASS 5, 10, 15, 20
Maximum short-circuit current breaking capacity (Icu)
at 400 V rated value50 000 A
at 500 V rated value50 000 A
EMC emitted interference acc. to IEC 60947-1CISPR11, ambience A (industrial sector)
EMI immunity acc. to IEC 60947-1corresponds to degree of severity 3, ambience A (industrial sector)
Conducted interference
due to burst acc. to IEC 61000-4-42 kV network connection / 1 kV control connection
due to conductor-earth surge acc. to IEC 61000-4-52 kV
due to conductor-conductor surge acc. to IEC 61000-4-51 kV
Protection against electrical shockfinger-safe
Main circuit
Number of poles for main current circuit3
Design of the switching contactelectromechanical
Adjustable pick-up value current of the current-dependent overload release0.15 ... 2 A
Type of the motor protectionfull motor protection
Operating voltage rated value360 ... 440 V
Operating current
at AC at 400 V rated value2 A
at AC-3 at 400 V rated value2 A
Operating power at AC-3
at 400 V rated value0.75 kW
at 500 V rated value750 W
Product function
digital inputs parameterizableYes
digital outputs parameterizableYes
Number of digital inputs4
Number of sockets
for digital output signals1
for digital input signals4
Number of digital outputs1
Supply voltage
Type of voltage of the supply voltageDC
Supply voltage 1 at DC rated value30 V
minimum permissible26.5 V
maximum permissible31.6 V
Control circuit/ Control
Type of voltage of the control supply voltageDC
Control supply voltage at DC
rated value20.4 ... 28.8 V
Control supply voltage 1
at DC rated value24 V
at DC rated value20.4 ... 28.8 V
at DC20.4 ... 28.8 V
Power loss [W] in auxiliary and control circuit
in switching state OFF with bypass circuit2.0736 W
in switching state ON with bypass circuit4.1184 W
Response times
Switch-on delay time85 ms
Off-delay time65 ms
Mounting positionvertical, horizontal, flat
recommendedhorizontal
Mounting typescrew fixing
Height215 mm
Width294 mm
Depth159 mm
Installation altitude at height above sea level maximum2 000 m
Ambient temperature
during operation-25 ... +55 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
Relative humidity during operation10 ... 95 %
Protocol is supported
PROFIBUS DP protocolNo
PROFINET protocolNo
Design of the interface
AS-interface protocolYes
PROFINET protocolNo
PROFIBUS DP protocolNo
Product function Bus communicationYes
Protocol is supported AS-interface protocolYes
Product function Control circuit interface with IO linkNo
Type of electrical connection of the communication interfaceM12 plug
Type of electrical connection
for main current circuitplug according to ISO 23570, HAN Q4/2
for auxiliary and control current circuitconnector
Type of electrical connection
1 for digital input signalsM12 socket
1 for digital output signalsM12 socket
2 for digital input signalsM12 socket
3 for digital input signalsM12 socket
4 for digital input signalsM12 socket
Type of electrical connection
at the manufacturer-specific device interfaceoptical interface
for device addressingM12 plug
for supply voltage line-sideM12 plug

External links