| Switch disconnector with fuse in new design Iu=250 A, Ue = 690 V, 3-pole for LV HRC fuse Sz. 1 and 2 with isolating contact strip for MCC with door operating mechanism 8UC7 Handle dark blue/blue-green Basic masking frame light gray |
Model |
Product brand name | SENTRON |
version | Complete version with rotary operating mechanism |
Design type | plug connector on the top |
Design of the operating mechanism | manual operating mechanism |
Type of the driving mechanism / motor drive | No |
Number of poles | 3 |
Size of disconnecting link | 2 and 1 |
Fuse system | LV HRC fuse |
Insulation voltage / rated value | 1 000 V |
Surge voltage resistance / rated value | 8 000 V |
Protection class |
Protection class IP | IP00 |
Dissipation |
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 11 W |
Electricity |
Operating current / at AC-21 / rated value | 250 A |
Continuous current / rated value | 250 A |
Let-through current / I2 t / maximum permissible / in utilization category / AC-22 B / at 400 V | 1 000 000 A²·s |
Main circuit |
Number of poles / for main current circuit | 3 |
Operating power | |
at AC-23 A / at 400 V / at 50/60 Hz / rated value | 132 000 W |
at AC-23 A / at 500 V / at 50/60 Hz / rated value | 132 000 W |
at AC-23 A / at 690 V / at 50/60 Hz / rated value | 185 000 W |
Operating voltage | |
at AC / at 50/60 Hz / rated value | 690 V |
at DC / rated value | 440 V |
Rated current Ie / maximum / in utilization category | |
AC-21 A / at 400 V | 250 A |
AC-21 A / at 500 V | 250 A |
AC-21 B / at 400 V | 250 A |
AC-21 B / at 500 V | 250 A |
AC-22 A / at 400 V | 250 A |
AC-22 A / at 500 V | 250 A |
AC-22 B / at 400 V | 250 A |
AC-22 B / at 500 V | 250 A |
Auxiliary circuit |
Number of CO contacts / for auxiliary contacts | 0 |
Number of NC contacts / for auxiliary contacts | 0 |
Number of NO contacts / for auxiliary contacts | 0 |
Suitability for use | |
EMERGENCY OFF switch | No |
safety switch | Yes |
Product feature / interlock | Yes |
Short circuit |
Conditional rated short-circuit current / in utilization category | |
AC-21 A / at 400 V | 100 kA |
AC-21 A / at 500 V | 100 kA |
AC-21 B / at 400 V | 100 kA |
AC-21 B / at 500 V | 100 kA |
AC-22 A / at 400 V | 100 kA |
AC-22 A / at 500 V | 100 kA |
AC-22 B / at 400 V | 100 kA |
AC-22 B / at 500 V | 100 kA |
Connections |
Connectable conductor cross-section | |
for main contacts | |
— stranded / maximum | 150 mm² |
Type of connection, main circuit | flat connector bottom connection, M10 |
Type of electrical connection | |
for main current circuit | flat connector |
Mechanical Design |
Height | 160 mm |
Width | 247 mm |
Depth | 279 mm |
Type of mounting | plug-in version |
Mounting position | any |
Mounting type | clip-on |
Mounting type | |
front mounting with 4-hole attachment | No |
front mounting with central attachment | No |
rail mounting | Yes |
Environmental conditions |
Ambient temperature | |
during operation / minimum | -25 °C |
during operation / maximum | 55 °C |
during storage / minimum | -50 °C |
during storage / maximum | 80 °C |