| SENTRON 3KC ATC6300; LCD; 144x144 mm; Transfer control device for control of MCCB, ACB, LBS; for load transfer between main and standby power supply Control panel instrument; Un 100...240 V AC 50/60 Hz, 110...250 V DC; Un 12...24 V DC Rated voltage Ue: 100...480 V AC 50/60 Hz; screw terminal connection Expandable by maximum 2 additional modules |
Model |
Product brand name | SENTRON |
Operating temperature | |
minimum | -30 °C |
maximum | 70 °C |
Switchover time / of the control device | 50 ms |
Overvoltage category | 3 |
Operating period / without auxiliary voltage supply | 300 s |
Insulation voltage (Ui) / at auxiliary power supply / at AC / rated value | 250 V |
Impulse withstand voltage (Uimp) / of the auxiliary power supply / at AC / rated value | 6 000 V |
Interference immunity duration / against voltage dip/sag / at AC / at 220 V | |
without expansion modules / maximum | 250 ms |
with 1 expansion module / maximum | 180 ms |
with 2 expansion modules / maximum | 120 ms |
Supply voltage / of the auxiliary power supply | |
at AC / Initial rated value | 100 V |
at AC / Final rated value | 240 V |
at AC / minimum | 90 V |
at AC / maximum | 264 V |
at DC / Initial rated value | 110 V |
at DC / Final rated value | 250 V |
at DC / minimum | 93.5 V |
at DC / maximum | 300 V |
Supply voltage / at DC power supply | |
Initial rated value | 12 V |
Final rated value | 24 V |
minimum | 7.5 V |
maximum | 33 V |
Protection class IP | |
on the front | IP40 |
Rear side | IP20 |
Apparent power consumption / at auxiliary power supply / at AC / at 240 V / maximum | 9.5 V·A |
Power loss [W] / at auxiliary power supply | |
at AC / at 240 V | 3.8 W |
at DC / at 250 V / maximum | 3.6 W |
Power loss [W] / at DC power supply | |
at 12 V / maximum | 3.2 W |
at 24 V / maximum | 2.9 W |
Consumed current / at DC power supply | |
at 12 V / maximum | 230 mA |
at 24 V / maximum | 120 mA |
Operating frequency / rated value | |
minimum | 45 Hz |
maximum | 66 Hz |
Number of CO contacts / for auxiliary contacts | 1 |
Number of NC contacts / for auxiliary contacts | 0 |
Number of NO contacts / for auxiliary contacts | 6 |
Product component / of the hardware real-time clock / Backup battery | Yes |
Number of slots | 2 |
Product component / RS 485 interface integrated | No |
Number of digital inputs | 6 |
Output voltage / at the relay outputs / at AC / maximum rated value | 250 V |
Input current / at digital input / with signal <0> / maximum | 8 mA |
Number of outputs / as contact-affected switching element | 7 |
Output current / at the relay outputs | |
at AC-1 / at 250 V / rated value | 8 A |
at AC-15 / at 250 V / rated value | 1.5 A |
at DC-1 / at 30 V / rated value | 8 A |
Switching capacity current / at the relay outputs / at DC / at 30 V / acc. to UL 508 | 1 A |
Mechanical service life (switching cycles) / of the relay outputs | 10 000 000 |
Electrical endurance (switching cycles) / of the relay outputs | 100 000 |
Input delay time | 0.05 s |
Insulation voltage (Ui) / of the relay outputs / rated value | 250 V |
Signal voltage | |
for signal <0> / at DC / Rated value | 2 V |
for signal <1> / at DC / Rated value | 3.4 V |
Impulse withstand voltage (Uimp) / of the relay outputs / rated value | 4 000 V |
Power frequency impulse withstand voltage / at the measurement inputs | 3 000 V |
Input impedance | |
between L and L / minimum | 1 MΩ |
between N and L / minimum | 0.5 MΩ |
Insulation voltage (Ui) / at the measurement inputs / rated value | 480 V |
Voltage measuring range / at the measurement inputs | |
between L and L / minimum | 50 V |
between L and L / maximum | 576 V |
between L and N / minimum | 50 V |
between L and N / maximum | 333 V |
Measured variable voltage | |
between L and L / Rated value | 480 V |
between N and L / Rated value | 277 V |
Relative measurement deviation | 0.25 % |
Impulse withstand voltage (Uimp) / at the measurement inputs / rated value | 6 000 V |
Supply voltage frequency / at the measurement inputs | |
minimum | 45 Hz |
maximum | 65 Hz |
Number of monitored phases | 3 |
Connectable conductor cross-section | |
minimum | 0.2 mm² |
maximum | 2.5 mm² |
acc. to UL 508 | |
— minimum | 0.75 mm² |
— maximum | 2.5 mm² |
AWG number / as coded connectable conductor cross section | |
minimum | 24 |
maximum | 12 |
acc. to UL 508 / minimum | 18 |
acc. to UL 508 / maximum | 12 |
Tightening torque [lbf·in] / with screw-type terminals / maximum | 5 lbf·in |
Tightening torque / with screw-type terminals / maximum | 0.56 N·m |
Height | 144 mm |
Width | 144 mm |
Depth | 43.3 mm |
Installation depth / with expansion module / maximum | 73 mm |
Net weight | 600 g |
Degree of pollution | 2 |
Ambient temperature / during storage | |
minimum | -30 °C |
maximum | 80 °C |