3EB5370-6AG30-0D RAILWAY SURGE ARRESTER 3EB5
From SIEMENS
3EB5 surge arresters Silicone housing, cage design. Rail application 25kV AC Applied standard: IEC60099-4 Fire test according to EN45545-2 Continuous voltage Uc: 30 kV AC Rated voltage Ur: 37 kV AC Up to 320 KM/H Nominal discharge current In: 10 kA Ures (10kA, 8/20µs): 87.0 kV Charge transfer rating Qrs: 2.0C Rated thermal energy Wth: 259kJ Rated short circuit current Is: 50 kA Creepage distance: 1250 MM Height: 391 MM Short-term load SSL: 2550N Hole circle diameter: 140-162 MM 3 drilled holes, Diameter: 12 MM Cardboard packaging | ||
Electrical data | ||
Standard | IEC 60099-4 | |
Designation / of arrester class | SM | |
Discharge current / according to IEC 60099-4 / rated value | 10.0 kA | |
Discharge capacity of electrical charge | 2.0 C | |
Voltage / rated value | 37.0 kV | |
Arrester continuous voltage | 29.6 kV | |
High current impulse / of arrester | 100.0 kA | |
Discharge short-circuit current / nominal value | 50.0 kA | |
Line frequency / rated value / minimum | 48.0 Hz | |
Line frequency / rated value / maximum | 62.0 Hz | |
Residual voltage | ||
at 1 kA / at (8/20) µs | 73.0 kV | |
at 3 kA / at (8/20) µs | 78.3 kV | |
at 5 kA / at (8/20) µs | 81.7 kV | |
at 10 kA / at (8/20) µs | 87.0 kV | |
at 20 kA / at (8/20) µs | 96.5 kV | |
at 125 A / at (30/60) µs | 66.1 kV | |
at 250 A / at (30/60) µs | 67.8 kV | |
at 500 A / at (30/60) µs | 69.6 kV | |
at 1 kA / at (30/60) µs | 71.3 kV | |
at 2 kA / at (30/60) µs | 74.8 kV | |
TOV withstand | ||
limited to 1 s | 39.8 kV | |
limited to 10 s | 37.0 kV | |
Rest lightning impulse voltage / of enclosure / at (1,2/50) µs | 225.0 kV | |
Power frequency impulse withstand voltage / of enclosure, rainy / limited to 1 min | 105.0 kV | |
Mechanical data | ||
Height | 391.0 mm | |
Creepage distance / of arrester | 1 250.0 mm | |
Flashover distance / of arrester | 394.0 mm | |
Net weight | 8.3 kg | |
Color / of the insulating body | grey | |
Shape of shed profile / of insulating body | Alternating | |
Specified long-term load (SLL) | 1 790.0 N | |
Specified short-term load (SSL) | 2 550.0 N | |
Accessories | ||
Type of electrical connection / for high voltage | Thread M16 and 2x M12 | |
Type of installation | 3 holes. Hole circle diameter: 140-162 mm | |
Pack type | Single | |
General data | ||
Ambient temperature / minimum | -50.0 °C | |
Ambient temperature / maximum | 60.0 °C | |
Installation altitude | 1 000.0 m | |
AL Code | N | |
ECCN code | N |